XGTD8-12 indoor environmental gas insulated metal-clad switchgear (hereinafter called "the panel") is a switchgear that filled with environmental gas with features of green and environmental friendly, reliable operation, reasonable design, small volume, free maintenance, long life and strong adaptability to environment.
The panel and its primary live parts are enclosed in stainless steel shell which free from the influence of outside. It adopts modular design to achieve the combination of same panel type and extended unit according to different schemes and arrangements. It can meet the demand of compact switchgear for secondary transmission and distribution substation. Also, I can be widely applied in secondary small distribution substation, industrial and mining enterprises, airport, railway, commercial district, high-rise building, expressway, subway, tunnel and other places with sever condition.
The product quality assurance is based on researching, developing designing and producing required by quality system and continues to improve. So it is completely complying with the newest version or revised version of following standard, but not limited to them.
GB3906 The 3.6 Kv-40.5 kV AC metal-enclosed switchgear and control equipment
GB/T11022 The high voltage switch equipment and control equipment
standards of common technical requirements
DL/T404 The 3.6 KV- 40.5 kV AC metal-enclosed switchgear and control equipment
GB/T1984 The high voltage AC circuit breaker
GB/T1985 The high voltage AC isolation and earthing switch
GB/T20840 Transformer part1: general technical requirements
GB /T11032 AC gapless metal oxides arrester
IEC62271-200 The rated voltage up to and including 1 kV 52 kV AC
metal-enclosed switchgear and control equipment
EN 50181 Rated voltage 1 kV-52 kV, current 250A- 2500A plug-in sleeve
for equipment
1.2 Service conditions
a. Ambient temperature: -45℃~+50℃the daily average value shall not exceed 35 ℃
b. Altitude: Not more than 4000m (If the equipment working over 1000m, please note it for the convenience of adjustment to the inflation pressure)
c. Relative humidity: Daily average is not more than 95%,
Monthly average is not more than 90%
d. Seismic grade: the seismic intensity shall not exceed grade 8
e. There shall be no Corrosive, flammable gases or other pollution
Note: if the service environment exceeds the above conditions, please consult with our company
Item | Unit | Parameters | |||
V: CB unit | C:load switch unit | ||||
Rated voltage | kV | 12 | |||
Rated current | A | 630/1250 | 630 | ||
Rated frequency | Hz | 50 | |||
1 min rated power frequency withstand voltage (RMS) | Phase to Phase Phase to earth | kV | 42 | ||
Insulation Distance | 48 | ||||
Rated Lightning impulse withstand voltage (peak) | Phase to Phase Phase to earth | kV | 75 | ||
Insulation Distance | 85 | ||||
Rated power frequency withstand voltage of auxiliary circuit | kV | 2 | |||
Rated short-circuit breaking current (RMS) | kA | 20/25 | |||
Rated short-circuit making current (peak) | kA | 50/63 | |||
Rated short-time withstand current (4s) | kA | 20/25 | |||
Rated peak withstand current | kA | 50/63 | |||
Main circuit resistance of each phase | μΩ | ≤160 | |||
N2 gas rated operation pressure | MPa | 0.02 | |||
Mechanical life | CB/ Load switch | times | 10000 | ||
Three-position switch | 5000 | ||||
Rated values of internal arc level(IAC) | KA/S | 25/0.5 | |||
N2 gas annual leak rate | % | ≤0.1 | |||
Degrees of protection | / | IP67 for gas-filled compartment, IP4X for others | |||