Overload Current Monitoring Relay 1 NC SCR Output Contact LED Indication
 
JDB-1 series motor protector is suitable for the control circuit of AC 45 ~ 60Hz, voltage 24V to 380V power supply circuit and AC contactor and other switch electrical appliances. When the main circuit of the motor has abnormal working conditions such as phase failure, overload, and three-phase unbalance, the protector can break the contact of the switch electrical appliance in time, disconnect the three-phase power supply of the motor, and quickly and reliably protect the motor.
The protector adopts the core-type current sampling detection technology, thyristor output, simple structure, convenient use, reliable operation, and has the advantages of no power consumption, long life, no arc generation during operation, and is ideal for motor protection. Electrical products
The protector meets the requirements of EN19474.7, EN60947-5, EN60204-1 standard GB14048.4.
 
(1) Protection functions: Phase protection, three-phase unbalance protection, and overload protection.
1. Phase-failure protection: When any phase of the three-phase power supply of the motor lacks a phase or the internal phase of the motor is broken, the action delay time of the protector is ≤ 1S.
2. Three-phase unbalance protection: When the phase difference of any two-phase working current in the three-phase power supply of the motor exceeds (50±10)%, the delay time of the protector operation is ≤1S.
3. Overload protection: When the operating current of the motor reaches 1.2 times to 6 times of the rated value, the action delay time of the protector is 80S ~ 10S (inverse time characteristic).
(B), the output interface reset mode: control circuit power reset; reset time: (60 ± 10) S.
(C), work methods: continuous work style.
(D), applicable voltage range: AC24V ~ 380V/45 ~ 60Hz.
 
♦ Features
Integrative structure Three-phase monitoring of overload, phase loss, phase unbalance Powered by the measuring circuit 1 NC SCR output contact  4 LEDs for status indication
 
♦ Protective Functions
Overload,Phase loss,Phase unbalance
 
♦ Typical Applications
 Pumps . Fans, Blowers , Motors, Compressors
 
 
♦ Approvals
CE • CCC
 
♦ Technical data
 

TypeJDB-1
Current range

2.5-5A,4-10A,8-20A,16-40A,32-80A,
63-160A,150-300A

Startup delay5s,10s,20s
Protective functionsoverload,phase loss,phase unbalance
Setting methodby knob
IndicatorsABC overload&phase loss
Output contacts1NC(SCR output)
Contact capacity1A 380VAC
Operating voltage of control loopAC220V or AC380V
Dimensions(H*W*D)

2.5-40A:38*90*63mm
80-300A:44.5*123*67mm

Mountingscrew fixing


 

Hot Products

120 Volt Overcurrent Current Balance Relay Integrative Structure For Blowers Protection function ...
Phase Unbalance Current Monitoring Relay Integrative Structure For Compressors ♦ Features -- ...
Fans current limiting relay , 40A Phase Failure Protection Relay Integrative Structure ♦ Features -- ...
Overload Current Monitoring Relay 1 NC SCR Output Contact LED Indication JDB-1 series motor ...
Unbalance Current Control Relay 220V 380V With Knob Setting Method With 4 LEDS 1 Features Integrativ...
Electronic Motor Current Monitoring Relay , 3 Phase Overcurrent Relay 220V 50Hz Technical Parameters ...