Product Details

RS2000E Double Clamp Digital Voltammeter Phase Tester

Product Description

 

RS20000E Double Clamp Digital Phase Meter is special designed for testing voltage, current and phase onsite, it is in high-precision, low price, portable hand-held, dual-channel input measuring products. It’s easy to measure the phase between U-U, I-I and U-I, identify the inductive circuit ,capacitive circuit and the phase sequence of three-phase voltage, detect the wiring group of transformer, test the secondary circuit and bus differential protection system, read the phase relationship among the CT groups of a differential protection system, and check if the watthour meter was correctly wired. When testing customers do not need cut off the measured circuit which input by split core current transformer. When measuring the phase between U1 and U2, the two input circuit loop are completely insulated isolation, so the possibility of misconnection is absolutely avoided, which may result in short circuit or even burn the meter. The device with high-contrast LCD screen, and the character in big size, which helps to obtain the best visual effects.

 

Product Features

 

  1. 1. Ingenious structure, easy to operate.

    A. hand held structure

    B. you should not disconnect the circuit or change the measurement range under 10mA-10A, 3V-500v.

    C. use high contrast LCD, character can be 25mm, the screen angle can be 700, to obtain the best visual effects

    D. the function and layout of the switch are reasonable, rotating can read the measuring voltage, current and phase.

    2. High resolution

    Adopt new type patent current clamp, current resolution up to 0.1mA; voltage resolution up to 0.1V.

    3. Low power consumption

    This product with micro power consumption design and with the function of testing the voltage of battery

     

 

Technical parameters
 

Intrinsic Error

Reference Working ConditionsTemperature(23±5)℃
Hunidity(45~75)%RH
Wave forms of measured signalsine wave,β=0.02
Frequency of measured signal(50±0.2)Hz
Position of Measured current carrying conductor in the nipper jawOptional position
Amplitude range of measured signal when measuring phase100~220V,0.5~1.5A
External reference frequency electromagnetic interferenceShould be avoided

 

Limits of Intrinsic Error

1 AC Voltage

Table 1:Measurement Error of AC Voltage
Measure rangeResolutionLimits of intrinsic error
20V0.01V±(0.3%RD+0.2% Range)
200V0.1V±(0.3%RD+0.2% Range)
500V1V±(0.3%RD+0.2% Range)

Input Impedance:2MΩ for all the measure range .

Voltage input impedance of phase testing: >500KΩ

2 Alternating current

Table 2:Measurement Error of alternating current
Measure rangeResolutionLimits of intrinsic error
200mA0.1mA±(0.3%RD+0.2)
2A1mA
10A10mA

3 Phases

U-U,U-I,I-I (see Table 3)

 

Table 3: Measurement Error of Power-frequency Phase
RangeResolutionLimits of intrinsic error
0~360°±2°

Impedance of input voltage loop when measuring phase of U1-U2:40KΩ

Operating error

Rated Working ConditionsTemperature(0~40)℃
Humidity(20~80)% RH
Wave forms of measured signalSine wave,β=0.05
Frequency of measured signal(50±0.5)Hz
Position of Measured current carrying conductor in the nipper jawOptional position.
Amplitude range of measured signal when measuring phasePhase U1-U2:30V~500V
Phase I1-I2:10mA~10.00A
Phase U1-I2 or I1-U2:10V~500V,10mA~10.00A
External reference frequency electromagnetic interferenceshould be avoided
Limits of Rated Working ErrorUnder the conditions described in 1, the limits of the rated operating error will not exceed twice of the limits of intrinsic error. 

 

Other technical features

Displaythree and half 
Sampling rate3 times per second 
Power supplySingle 9V laminated cell,current of power is less than 5mA 
DimensionsMeter shell192×95×55mm3
Clamp shell140×42×20mm3
Nipper jawΦ7mm×9mm
WeightMeter body280g
Measuring clamps2×200g
Storage ConditionsTemperature-10℃~50℃

Hot Products

RS2000B Double Clamp Digital Phase Meter Phase Tester Product Description RS20000B Double Clamp ...
RSCR2000 Handheld Clamp Digital Earth Resistance Meter Tester Product Description RSCR2000 series ...
RS2000E Double Clamp Digital Voltammeter Phase Tester Product Description RS20000E Double Clamp ...
RSZZ-50A Transformer DC Resistance Meter Product Description DC resistance measurement of transforme...
RSGM-5kV adjustable insulation resistance meter Product Description With the rapid development of ...
RSBX-H Sweep Frequency Response Analyzers Product Description RSBX-H tester based on the measurement ...