Home Companies Beijing GFUVE Electronics Co.,Ltd.

50/1A cast resin 5P20 class protection current transformer for distance protective relay

Beijing GFUVE Electronics Co.,Ltd.
Active Member

Contact Us

[China] country

Address: 01117-8 Fortune Street No.67 Chaoyang Road, Chaoyang District, Beijing, China.

Contact name:Andy

Inquir Now

Beijing GFUVE Electronics Co.,Ltd.

50/1A cast resin 5P20 class protection current transformer for distance protective relay

Country/Region china
City & Province beijing beijing
InquireNow

Product Details

50/1A cast resin 5P20 class protection current transformer for distance protective relay​

 
LZCG930-10 high precision protectioncurrent transformer is suitable for microcomputer protection of electrical equipment in 10KV and 35KV AC power system. It is widely used in not only compact fully insulated ring network switchgears such as ABB-SafeRing/ SafePlus,  Uniswitch,  Schneider  RM6, SM6, Siemens 8DJ10/8DH10, Simosec, FBX, Fluokit, Omar Garbo GA, GAE; SEL TPS(Q); VEI Unifluorc; Eaton SVS/12 ring network, but also cable distribution boxes because of its small size, light weight, openable and convenient installation.
 

The protection current transformer is used to reduce the currents in power systems, producing proportional currents in the unit’s secondary windings that remain isolated from the main circuit. The replica current is then used as an input to a protective relay, which can then automatically isolate part of the power circuit should it experience a fault.

 

Protection Current Transformers are designed to measure the actual currents in power systems and to produce proportional currents in their secondary windings which are isolated from the main power circuit.

 

protection cts are used for protection against over current or faulty current, their secondary is

thusconnected to the protection relays and the to the tripping coil. there may be series or shunt

tripmechanism, thus the burden(VA) of protection ct is more as compared to metering cts.

 

The classification of protection current transformers follows the following simple formula: "10 P10" Manufacturers of protection devices will normally specify the classification for the

protection current transformer intended to operate the particular protection device concerned.

 

This is required for protection CT, because the fault current is high and the CT should be able tosense the high fault current accurately to protect the system. The common numbers are 10, 15, 20 and 30. Class PS: PS is for 'Protection Special'. This class of CT's are used for special

Protection such as differential protection, distance.

MODEL MEANING

Cast resin straight-through current transformer

WIRING DIAGRAMS

Cast resin straight-through current transformer
P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).

PARAMETERS

Technical parameters 
StandardsIEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006
Rated primary current30-1000A
Rated load≤20VA
Rated frequency50Hz or 60Hz
Rated secondary current5A or 1A
Rated short-time thermal current40kA, 1S
Rated continuous thermal current120%I1n
Secondary winding power-frequency voltage3kV, 1min
Instrument security factorFS ≤10
Mechanical parameters 
Dimensions (W×D×H) (mm)φ45xφ120x65
Weight (kg)2.1
Operating conditions 
Operating temperature-35°C to +55°C
Daily average temp<+40°C
Altitude<3500 meters
Operating conditions - continued 
ConditionNo existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

TypeLZCG530-10LZCG530-10LZCG530-10
PurposeMeasuring current transformerProtection current transformerDouble winding current transformer
Rated primary current (AMP)Accuracy class and rated load(VA)Accuracy class and rated load(VA)Composite accuracy class and rated load(VA)
0.2S0.20.510P2010P1510P100.2S0.510P1510P10
30  2       
40  2.5       
50  3.75  2    
75 3.755 23.75    
1002.557.5 2.53.75    
15057.5102.53.756.252.53.75 2.5
2007.510153.7557.557.5 3.75
30010152057.5107.5102.55
4001520256.257.5151012.53.755
5002025256.257.51515153.755
6002030307.5102015203.757.5

SELECTION GUIDE

ModelPrimary rated currentRated loadAperture (mm)Description (mm)Weight (kg)MaterialWater-proof
LZCK-55100-1500A≤10VAφ55180×138×522PCIP65
LMCK185-10300-3000A≤25VAφ185350×283×554.5PCIP65
LZCK310-10300-600A≤10VAφ50φ50 x φ110 x 321Resinsilicon case (option)
LZCK322-1030-600A≤10VAφ50φ50 x φ110 x 521.6Resinsilicon case (option)
LZCK350-1020-600A≤25VAφ50φ50 x φ110 x 1053.1Resinsilicon case (option)
LZCG930-1030-600A≤20VAφ45φ45 x φ120 x 652.1Resinsilicon case (option)
 


 



Hot Products

50/1A cast resin 5P20 class protection current transformer for distance protective relay​ LZCG930-10 ...
LZCK-55 Current transformer split core outdoor IP67 200/5a 0.5s 5m cable for Distribution transforme...
GF302D1 Portable Three Phase Power & Energy Calibrator Three power phases in a single easy-to-use ...
GF6018A 1000A 20A AC DC portable programmable multi-function power source GF6018A Programmable Multi...
GF6018A High Precision AC DC Multi-function Programmable Electrical Calibration of multimeter GFUVE' ...
GF302D AUTOMATIC THREE PHASE Energy Meter testing on-site and in laboratory The GF302D energy meter ...