Product Details

0.5 Grade Orange LCD display Intelligent 400V 200Kw Load Bank
 
Product Description
 

1.our load bank an accurately test output power and load capacity with all kinds of generators.

2.System consists of testing/control and load bank, mainly includes AC load bank, data capture system, auto load/unload control system, heat dissipation device, assist control and PC software.

3.User can control load bank through local control panel, also through software

 

Technical Parameters

 

Rating Voltage/Frequency200Kw at 400VAC, 3 phase 4 wire, 50 Hz, 
Max Load PowerResistive load:200kW
Load Steps1kW,2kW,2kW,5kW,10kW,20kW,20kW,50kW, 100kW,min load step: 1 kW
PF(Power Factor)1
Load Accuracy (each step)±5%
Load Accuracy (overall)3%
Display Precision0.5 grade
Control Power220VAC, 1 phase 50 Hz, 
Wire Connection

Load power supply input——busbar

Control power supply input——three pin socket

InsulationF
Way of WorkingContinuous Work
CoolingFan forced cooling, horizontal inlet air and vertical outlet cooling
Casing ColorGrey(RAL7035)
Dimensions1450 mm*900mm*870mm(length*wide*high)
WeightAbout 750kgs
Temperature-10℃~+50℃
Relative Humidity≤95%
Altitude≤1500 meter
ContactorSchneider
FuseDELIXI
Alloy Resistance(self-developed)

 


Product Advantage
 

Communication type: through RS232, RS485

Load mode: manual load or automatic load.

Manual load: input power and power factor.

Automatic load: User can set several periods of power and time, and in turn of 0%→25%→50%→75%→100%, etc preset order to make automatic load testing.

Parallel testing: when several load banks parallel working, parameters of each load bank can be displayed and recorded, so do the final parameters of paralleling working.

 

Application
 

1.Manufacturers of standby power generators commonly use load banks to test and tune newly assembled units

2.generator has been set up in a test cell within the factory, a test engineer uses the load bank to apply a discrete, selectable electrical load to the generator and measure the response stability and endurance.

3.During this process, the test engineer calibrates and adjusts the generator performance to ensure it meets the intended product specifications and tolerances.

 

 

 
 

Hot Products

LCD display Intelligent 400V 200Kw Load Bank 0.5 Grade Orange Product Description The system can ...
0.5 Grade Orange LCD display Intelligent 400V 200Kw Load Bank Product Description 1.our load bank an ...
LCD display Intelligent 400V 200Kw Load Bank For Generator Testing Product Description The system ...
LCD display Intelligent 400V 200Kw Dummy Load Bank For Generator Testing Product Description 1.our ...
Anti Corrosion Materials Professional Produce AC Load Bank Accurate Product Description The system ...
Anti Corrosion Materials Professional Produce AC Load Bank For Generator Testing Product Description ...