Home Companies Hebei Kaixiang Electrical Technology Co., Ltd

Professional Portable Dummy Load Bank 900kw Metal Alloy Materials

Hebei Kaixiang Electrical Technology Co., Ltd
Active Member

Contact Us

[China] country

Address: No33 Wangshan Road, Green Island Economic Development Zone, Shijiazhuang, China

Contact name:

Inquir Now

Hebei Kaixiang Electrical Technology Co., Ltd

Professional Portable Dummy Load Bank 900kw Metal Alloy Materials

Country/Region china
City & Province shijiazhuang hebei
InquireNow

Product Details

Portable dummy load bank 900kw for generator UPS testing

 

Introduction

 

AC400-900KW Portable Load Bank In Automaticlly combine the dry type load module with automatic measurement and control module, it can accurately test output power and load capacity of all kinds of generators, offer scientific and high efficiency testing method for large power generator set.It is composed of measurement & control part and load part, mainly including dry type AC load bank, data acquisition system, auto load/unload control system, cooling system, auxiliary control etc.

 

Applications

 

overheating protection: when temperature is over the safe value, it can unload automatically and give an alarm.

fan interlock protection: load bank cannot add any load when working power of fan is off.

emergency stop: you can press the Emergency Stop switch in the panel, when the load bank is locked in this state, it cannot add any load.

overvoltage protection: when input voltage is over the safe value, it can unload automatically and give an alarm.

short circuit protection: when short circuit, fuses in the load bank can insure to unload automatically.

 

Technical specification

 

AC400-900kW Automatic Load Bank
Rating Voltage/Frequency

400VAC, 3 phase 4 wire, wire voltage 400V, phase voltage 230V

50Hz

Rated Load PowerResistive load: 900kW
Installed CapacityResistive load: 900kW
Load Step1,2,2,5,10,10,20,50,100,100,200,200,200kW, min step load: 1kW
PF(Power Factor)1
Load Tolerance (each step)±5%
Load Tolerance(overall)±3%
Display Precision0.5 class
Control PowerExternal 380VAC/50Hz, 3 phase 4 wire, 220V 1-phase
Wire Connection

Load power supply input——Copper bar (star coupling)

Control power supply input——Connector-bar

InsulationF
Duty CycleContinuous
Cooling TypeForce air cooling, horizontal air inlet and vertical air outlet
TransportationHoisting, there are lifting lug on top and castors at the bottom of casing
DimensionAbout 2440mm*1400mm*1680mm(L×W×H)
WeightAbout 1200kgs
Casing ColorGrey(RAL7035)or as required
Operating Environment Parameter
WorkplaceIndoor
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Altitude≤1500 meter
Atmospheric Pressure86~106kPa
 

Main features

Local Control: There is local control panel with several power steps; user can load / unload by button.

Intelligent Control: Through data processing software in PC, user can make automatic load, to display, record and manage the testing data, to form curves, tables, also to print them.

Control Pattern interlock, there is control pattern switch, when choose one control pattern, operation of other pattern is invalid, avoid the clash.

Local meter display data: local meter can display 3 phases voltage, current, active power, frequency and so on.

Load testing: load power that not beyond the rated power, testing and display stable state 3 phases voltage, current, active power, frequency, working time, etc of generator sets.

Load / unload with one key: Whether manual control, remote control or software control, user can preset the power, then press load master button. Load bank loaded according to preset power to avoid load fluctuation during the power changing.

Control Pattern: user can choose local control and intelligent control.

 

 

Hot Products

1200kw resistive load bank for generator UPS inverter testing Introduction AC400-1200kW is of ...
1000kw load bank resistor for generator UPS testing Introduction AC380-1000kW is of independent ...
Portable dummy load bank 900kw for generator UPS testing Introduction AC400-900KW Portable Load Bank ...
Electronic load bank 700kw for generator UPS inverter testing Introduction AC380-700kW is of ...
Variable resistive load bank 500 Kw for testing generator UPS Transformer Introduction The system ...
600 KW portable ac load bank for generator UPS Transformer testing Introduction 1,AC400-600kW ...