Home Companies Hebei Kaixiang Electrical Technology Co., Ltd

1500 KVA Apparent Power Dummy Load Bank Cabinet For Battery System Testing

Hebei Kaixiang Electrical Technology Co., Ltd
Active Member

Contact Us

[China] country

Address: No33 Wangshan Road, Green Island Economic Development Zone, Shijiazhuang, China

Contact name:

Inquir Now

Hebei Kaixiang Electrical Technology Co., Ltd

1500 KVA Apparent Power Dummy Load Bank Cabinet For Battery System Testing

Country/Region china
City & Province shijiazhuang hebei
Categories Uninterrupted Power Supply (UPS)
InquireNow

Product Details

1500 KVA Apparent Power Dummy Load Bank for genset UPS testing

Introduction

 

Triumph load are available in stationary type for permanent installation or portable type with fork lift pocket base, castors. Larger load banks, typically above 1500kVA, are based on an ISO container construction. Special finishes including custom paint colors and stainless steel casings can be supplied.

Tailor-made load banks can be supplied for most powers, voltages, frequencies and sizes. Multi-voltage load banks are also available for operation over a large voltage range. At the same time, It can operate in parallel with more than two units.

Triumph load can simulate the real working conditions and provides a rigorous test regime for power supplies from 1kW to 60MW. Resistive, inductive(reactive),capacitive or combined load banks can be customised for any application. They can be used for testing numerous sets in a workshop environment, or used for on-site commissioning, witness tests and proof trials.

 

Application

 

AC430-1500kvA Dummy Load Bank can be used in a wide variety of applications, such as

1. Ups system testing

2. Battery system testing

3. Load optimization in prime power applications

4. Factory testing of turbines

5. factory testing of engine generator sets

6. To reduce wet stacking problems

7. Periodic excercising of stand-by engine generator sets

Technical specification

System Parameter
Rating voltage/frequency430v, 3 phase 4 wire 50Hz
Max Load Power

Apparent Power: 1500KVA

Resistive Load: 1200kW

Inductive Load: 900KVAR

Load Resolution

Resistive Load: 14 steps 1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100kW,200kW,200kW,200kW, 200kW, 200kW

Inductive Load: 13 steps

1KVAR,2 KVAR, 2KVAR, 5KVAR, 10KVAR, 10KVAR, 20KVAR, 50KVAR, 100KVAR, 100KVAR,200KVAR,200KVAR,200KVAR

Power Factor0.8(lag)
Load Tolerance (each step)±5%
Load Tolerance (overall)±3%
Fan &Control VoltageExternal AC 3 phase 4 wire,380V/50Hz
Wire Connection

Load bank input——Copper bar (star coupling ”Y”)

Control power input——Connector-bar

Communication InterfaceRS485,RS232
InsulationF
Max Protection GradeIP54
Duty CycleContinuous
CoolingForced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling
EnclosureContainer type,with a ladder, air inlet and outlet with mesh enclosure and protection door
Internal LightingAdequate internal lighting will be provided
TransportationHoisting, there are lifting lug in top of casing
ColorGrey RAL7035 or as required
DimensionsAbout 4000mm×2350mm×2591mm(L×W×H)
Operating Environment Parameter
WorkplaceOutdoor
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Atmospheric Pressure86~106kPa
Brands of Main Components
ContactorSchneider
FuseMiro
PLCSiemens
Alloy ResistorKaixiang
Data Processing SoftwareKaixiang
 
Main features

(1) Overvoltage Protection: the input load voltage is over the safe threshold value, system unload automatically and give an alarm.

(2) Short Circuit Protection and Over Current Protection: when short circuit, fuses in the load bank can insure to unload automatically.

(3) Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.

(4) Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.

(5) Fan Delivery Protection: insufficient air volume with any fan 2450m³/h, system unload automatically and give an alarm.

(6) Overload protection with fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.

(7) Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.

(8) Protection Switch: some protection with switch, when misinformation or in special need, user can close the corresponding protection function temporarily.

(9) Safety Monitor: through indicator lights on main interface, user can monitor system state. When system abnormally stop and protect, software interface prompt the cause immediately.

 

 

 

 

 

 

 

Hot Products

AC400-500kW Dummy Load Bank With Frequency 50HZ And Best Sales Introduction AC400-500kW Dummy Load ...
3 Ph 300 KW Portable Resistive Load Bank AC Electronic Load Bank Introduction AC400-300kW Dummy Load ...
1000 Kva Inductive or Resistive Dummy Load Bank for generator testing Introduction AC400-1000KVA ...
625KVA resistive inductive load bank for Genset UPS testing Introduction 1 System can work with PC ...
1500 KVA Apparent Power Dummy Load Bank for genset UPS testing Introduction Triumph load are ...
Introduction Dummy load bank main used to test the capability and aging degree for high-power ups on...