Home Companies Hebei Kaixiang Electrical Technology Co., Ltd

600 KVAR Portable Reactive Load Bank AC400 Grey Surface ISO Standard

Hebei Kaixiang Electrical Technology Co., Ltd
Active Member

Contact Us

[China] country

Address: No33 Wangshan Road, Green Island Economic Development Zone, Shijiazhuang, China

Contact name:

Inquir Now

Hebei Kaixiang Electrical Technology Co., Ltd

600 KVAR Portable Reactive Load Bank AC400 Grey Surface ISO Standard

Country/Region china
City & Province shijiazhuang hebei
Categories Uninterrupted Power Supply (UPS)
InquireNow

Product Details

600 KVAR portable reactive load bank for generator testing
Introduction

1 System mainly consists of resistance load, data collecting, control system, cooling device, etc. The system can test output power and load performance of generator sets.

2 System can load power in rated range, measure generator steady-state 3 phase voltage, current, active power, power factor, frequency, and running time, and simulate the generator set real load working state. Power input using sectional type, energy dissipation type load, forced-air cooling, 3 phase fan decentralized supply air, air-flow is sufficient and low noise.

3 The system is a self-developed device used for electricity load testing by Kaixiang Technology. It perfectly combines the high voltage dry type load module and measurement and control module, precisely test output power and load performance of kinds of generator set.

Applications

(1) Installation: Check installation environment , the machine should be placed in the open, flat, safe environment, the bottom four corners must be flat, sturdy sleepers paving to reduce vibration during operation, and improve the reliability of the ground.

(2) Ventilation inspection: Turn on all the ventilation doors of machine, including the top door and side door, and then fixed. Observe if all vents are normal, whether the foreign body obstruction, whether the surroundings neat and clean, near unit will not hinder ventilation debris, make sure the duct patency.

Technical Specifications

System Parameter
Rating voltage/frequency400V, 3 phase 4 wire 50Hz
Max Load PowerInductive Load: 600KVAR
Load Resolution

Total 645KVAR @415V 3 phase 4wire,50HZ

1KVAR,2 KVAR, 2KVAR, 5KVAR,5KVAR, 10KVAR, 10KVAR, 20KVAR, 20KVAR,20KVAR, 50KVAR, 100KVAR,200KVAR,200KVAR

Total 600KVAR @ 400V 3phase 4wire, 50HZ

0.93KVAR,1.86KVAR, 1.86KVAR, 4.65KVAR, 4.65KVAR,9.3KVAR, 9.3KVAR, 18.6KVAR, 18.6KVAR,18.6KVAR,46.5KVAR, 93KVAR,186KVAR,186KVAR

 

Load Tolerance (each step)±5%
Load Tolerance (overall)±3%
Fan &Control VoltageExternal AC 3 phase 4 line, 380V/50Hz
Wire Connection

Load bank input——Copper bar (star coupling ”Y”)

Control power input——Connector-bar

Communication InterfaceRS485,RS232
InsulationF
Max Protection GradeIP21
Duty CycleContinuous
CoolingForced air cooling, by Axial Fan; horizontal inlet air, horizontal air outlet
TransportationHoisting, there are lifting lug in top of casing
ColorGrey RAL7035 or as required
Operating Environment Parameter
WorkplaceIndoor or outdoor with canopy
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Atmospheric Pressure86~106kPa
Brands of Main Components
ContactorSchneider
FuseMiro
PLCSiemens
Alloy ResistorKaixiang
Data Processing SoftwareKaixiang
 
 
Main features

Intelligent Loading: after setting generator rated power in software, system realize rapid loading through preset proportion, automatically and continuously load multiple power value and common tests, like stepping, full load, and over load, so that improve working efficiency. High Efficiency Data Management: display real-time testing data, generate curves graphs automatically, also can put data into storage. According to generator set No. set up testing file, support to query at any time, and improve data management efficiency.

Comprehensive Protection Function: multiple protection, like over temperature, smoke. When in danger, automatically terminate the test and give alarm to protect safety of personnel and equipment.

Stable Running: with the latest generation control module as the core, a sharp rise in system response speed and anti-interference performance, avoid function failure in complex electrical environment, and ensure system running stably and reliably.
New Load Bank Technology: using the international advanced AC load bank technology, overcome the old water bank defects, such as bear bumpy, unable to use when go to sea, realize Mooring Trial and Sea Trail, and simulate the real working condition of generator running.

Mature Manufacturing Technology: load element using excellent anti-corrosion materials; waterproof insulation container packaging, suitable for adverse environment such as ocean. Internal layout is reasonable, air channel is clear, rapid heat emission, and satisfy continuous working need.

High Power Load: high load power density, large capacity of single set, parallel running to finish super power testing, and realize tens of megawatts of power loading.

Accurate Data: with high precision data collection module and measuring meter, related equipment has passed the certification by CMA (China Metrology Accreditation) qualification testing institution, and ensures the reliability of data.

Flexible Control Mode: based on different using habit, several control modes as following can be choose, local panel operation, remote box controlling, and intelligent software.

 

 

 

 
 

Hot Products

Inductive load bank 250kva for generator UPS, transformer,testing Introduction 1 The system is a ...
Reactive load bank 1500kva power banks for generator testing Introduction 1 System can load power in ...
Dummy load bank 3546kva inductive power banks for generator testing Introduction (1) According to ...
Power banks 4375 KVA Reactive Load Bank for generator testing Introduction 1 System can load power ...
600 KVAR portable reactive load bank for generator testing Introduction 1 System mainly consists of ...
electronic power banks 271kVA inductive load bank for generator testing Introduction According to ...