16A-100A Rated Residual Current Circuit Breaker electrical rccb With ISI Mark

Country/Region china
City & Province zhejiang
Categories Battery Chargers
InquireNow

Product Details

16A-100A Rated Residual Current Circuit Breaker electrical rccb With ISI Mark

VKL11 Residual Current Circuit Breaker RCCB with ISI mark​

 

1. General

 

1.1 RCCB Function

 

Control electric circuits.

Protect people against indirect contacts and additional protection against direct contacts.

Protect installations against fire hazard due to insulation faults.

Residual current circuit breakers are used in housing, tertiary sector and industry.

 

1.2 RCCB Selection

Detectable wave form

 

AC class

Tripping is ensured for slowly increasing sinusoidal AC residual currents

 

A class

Tripping is ensured for sinusoidal AC residual currents and for pulsed DC residual currents, whether applied suddenly or increasing slowly.

 

ASi Type - Full type A features + Si: Super immused (High immunity to unwanted tripping)

Tripping is ensured not only for sinusoidal AC residual currents but also for pulsed DC residual currents whether applied suddenly or increasing slowly. S, G/SI type with filters against spurious tripping caused by harmonics and transient surges. With the impact of 8/20us surge 3000A, this high immunity RCCB will still be in stable status.

Note: Our ASi type includes G/KV function and Si function.

 

 

1.3 RCCB Approvals and certificates

We certify that the RCCB has been tested for the following routine tests as per IS: 12640 (Part 1):2016 and found to be complying

with the requirements.

1. Verification of the operating characteristic as per Seq. - D0 CL9.9

2. Verification of the operation of the test device at the limits of rated voltage as per Seq. - D1 CL9.16

3. High Voltage Test as per D.3 of Annex D

4. Test for standard values of break time and non- actuating time as per CL 5.3.12 (table -1)

 

Tripping sensitivity

10mA - precision instrument leakage protection and bathroom use.

30mA - additional protection against direct contact.

100mA - co-ordinated with the earth system according to the formula I△n < 50/R, to provide protection against indirect contacts;

300mA/500mA - protection against indirect contacts, as well as fire hazard.

Tripping time

Instantaneous

It ensures instantaneous tripping(without time-delay).

Short time delay ASi

(High Immunity/ Avoid nuisance tripping &blinding)

It ensures any tripping at least 10ms.

Selective

It ensures total discrimination with a non selective RCD placed downstream.

 

 

 

RCCB | Residual Current Circuit Breaker

 

2. Technical parameters

 StandardIEC/EN 61008-1 AS/NZS61008.1
Electrical featuresModel No.VKL11
Poles2P, 4P
Rated current In16A, 25A, 32A, 40A, 63A, 80A, 100A
Rated Sensitivity I△n10mA(2P/4P 16A,25A.32A/40A), 30mA, 100mA, 300mA
Rated voltage Ue2P: 240V 4P: 415V
Insulation voltage Ui415V
Rated frequency50/60 Hz
Rated residual making and breaking capacity I△m1500A
Short-circuit current Inc=I△c6000A, 10000A
Type (wave form of the earth leakage sensed)AC, A, ASi, S
break time under I△n≤0.1s(Normal type), 10ms~300ms(ASi type). 150ms~500ms(S type)
Rated impulse withstand voltage(1.2/50) Uimp4kV
Dielectric test voltage at ind. Freq. for 1 min2.5
Pollution degree2
Mechanical featuresElectrical life≥2000
Mechanical life≥2000
Fault current indicatorYes
Terminal protection degreeIP20

Ambient temperature (with

daily average≤35℃)

-25℃ to 50℃
Storage temperate-30℃ to 70℃
InstallationTerminal connection typeCable/Pin-type busbar
Terminal size top/bottom for cable25-35 mm²
18-3/18-2 AWG
Terminal size top/bottom for busbar10/16 mm²
18-8/18-5 AWG
Tightening torque2.5 N·m
22 In-Ibs.
MountingOn DIN rail EN 60715 (35mm) by means of fast clip device
ConnectionFrom top and bottom

 

 

3. RCCB Outline and installation dimensions (mm)

 

Product Description:

Residual Current Circuit Breaker (RCCB) is a reliable device used to protect people from electric shock and safeguard electrical appliances from damage. It is widely used in commercial and residential buildings for overload or short circuit protection. The RCCB type EV is equipped with the latest safety features, which makes it a preferred choice for protecting people and their household appliances. It is certified by CE, ISI, NF, SEMKO, VDE and KEMA, offering superior performance and excellent safety ratings.

The RCCB is rated with an Impulse Withstand Voltage of 4kV. It also features a Rated Service Short-Circuit Breaking Capacity of 6kA and a Rated Operating Duration of ≤1s. These impressive ratings ensure the reliability and safety of the device against overloads, short circuits, and electrical shocks.

The RCCB is designed to automatically detect and trip in the event of an earth leakage or over-current fault. This helps protect people and electrical appliances from potential harm and damage. It also helps reduce the risk of fire and electrical shocks due to short circuits or over-currents. The RCCB is easy to install and highly reliable, making it an ideal choice for home and office use.

 

Features:

  • Product Name: Residual Current Circuit Breaker RCCB
  • Rated Service Impulse Withstand Voltage: 6kV
  • Certificate: CE, ISI, NF, SEMKO, VDE, KEMA
  • Rated Residual Operating Current: 30mA-100mA
  • Rated Service Short-Circuit Breaking Capacity: 10kA
  • Rated Operating Frequency: 50/60Hz
  • Residual Current Circuit Breaker Type: EV
  • Residual Current Circuit Breaker with ISI Mark: Yes
  • Residual Current Circuit Breaker NF SEMKO VDE KEMA: Yes
 

Applications:

HAROK's VKL11 Residual Current Circuit Breaker (RCCB) is a reliable and efficient electric shock protection device that is compliant with the highest safety standards. It has been certified by NF, SEMKO, VDE, KEMA, ISI, and CE, and is the ideal choice for any application that requires superior shock protection. The VKL11 RCCB is highly reliable, featuring a rated frequency of 50/60Hz, a rated residual current off-time of ≤0.1s, a rated service impulse withstand voltage of 6kV, a rated insulation voltage of 500V, and a rated residual operating current of 30mA-100mA. This product has a minimum order quantity of 5000, and is packaged in paper cartons. It is available in a variety of sizes and configurations, and can be ordered in bulk with a 4-6 week delivery time after payment. HAROK also guarantees a supply capacity of 100,000 PCS PER MONTH. All HAROK products are RoHS compliant and have the ISI mark of reliability and safety.

 

Technical Parameters:

Product AttributeSpecification
Rated Residual Current Off-Time≤0.1s
Rated Current16A-100A
Rated Service Impulse Withstand Voltage6kV
Rated Impulse Withstand Voltage4kV
Rated Insulation Voltage500V
Rated Service Short-Circuit Breaking Capacity10kA
Rated Voltage230V AC
Rated Operating Frequency50/60Hz
Rated Residual Operating Current10mA-300mA
Rated Frequency50/60Hz
TypeResidual Current Circuit Breaker type AC, type A, type ASi, Residual Current Circuit Breaker NF SEMKO VDE KEMA, Residual Current Circuit Breaker RCCB
 

Customization:

Residual Current Circuit Breaker RCCB
  • Brand Name: HAROK
  • Model Number: VKL11
  • Place of Origin: CHINA
  • Certification: NF, SEMKO, VDE, KEMA, ISI, CE
  • Minimum Order Quantity: 5000
  • Packaging Details: PAPER CARTON
  • Delivery Time: 4-6 weeks after payment
  • Payment Terms: FOB NINGBO or SHANGHAI
  • Supply Ability: 100,000 PCS PER MONTH
  • Residual Current Circuit Breaker type EV
  • Residual Current Circuit Breaker Inmetro
  • Residual Current Circuit Breaker type EV RCCB
  • Rated Short-Circuit Breaking Capacity: 4kA
  • Rated Service Impulse Withstand Voltage: 6kV
  • Rated Voltage: 230V AC
  • Rated Current: 30mA-100mA
  • Rated Operating Duration: ≤1s
 

Packing and Shipping:

Packaging and Shipping for Residual Current Circuit Breaker (RCCB):

The RCCB should be packed in a correctly sized cardboard box or suitable packaging material. The box should be sealed and labeled with the product name, weight, and dimensions.

The box should be placed in a larger box, filled with packing materials such as bubble wrap or packing peanuts, to protect the product during shipping. The larger box should be labeled with the product name, weight, and dimensions.

The product should be shipped with a reputable shipping service, such as UPS or FedEx, and should include a tracking number. The customer should be provided with the tracking number and estimated delivery date.

Hot Products

40a 300ma rccb 500V Residual Current Circuit Breaker Type A EV VKL11 Residual Current Operated ...
16A-100A Rated Residual Current Circuit Breaker electrical rccb With ISI Mark VKL11 Residual Current ...