CT PT Analyzer HYVA-404


Tests for Current Transformer:
 
1  Excitation curve and parameters test
2  Turns ratio test
3  Ratio and phase error test
4  Polarity mark check
5  Winding resistance measurement
6  Secondary loop burden measurement
7  Error line curve test for protection CT
8  Transient CT parameters test
9  CT nameplate guess
10  Saturation hysteresis loop curve measurement
 
Tests for Voltage Transformer:
 
1  Turns ratio test
2  Ratio error and phase angle error test
3  Polarity test
4  Secondary burden test
5  Winding resistance test
 
Applications of CT/ PT Analyzer:
 
1  CT nameplate check
2  CT parameters check in work burden
3  CT transient parameters analysis
4  CT ratio and phase error calibration
5  PT routine test

1  Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
2  Power supply: AC220V±10%, 50/60Hz±10%
3  Voltage output: 0.1~180V (AC)
4  Current output: 0.001~5A(RMS)
5  Power output: 500VA
6  Maximum knee voltage measurement: 45KV
7  Current measurement:
    Range: 0~10A (automatically change range in 0.1/0.4/2/10A) 
    Error: <±0.1%+0.01%FS
8  Voltage measurement:
   Range: 0~200V (automatically change range in 1V/10V/70V/200V)
   Error: < ±0.1%+0.01%FS
9  Turns ratio measurement:
     Range:1~35000
     1~2000     error<0.05%
     2000~5000  error<0.1%
     5000~35000  error<0.2%
10 Phase measurement: error: ±2min; resolution: 0.01min
11 Winding resistance measurement: 
      Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
      Error: < 0.2%RDG+0.02%FS
      Maximum resolution: 0.1mΩ
12 Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
13 CT Secondary burden:
      Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
      Error: <0.2%RDG+0.02%FS 
      Maximum resolution: 0.001ohm
14 PT Secondary burden:
      Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
      Error :<0.2%RDG+0.02%FS 
      Maximum resolution: 0.1ohm
15 PT ratio measurement:
      Range: 1~35000
      1~10000 error<0.1%
      10000~35000 error<0.2%
16  PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%
17  PT phase angle measurement: maximum error < 3min
18  Make evaluation for test results according to selected standards
19  Make word report for test result
20  Make word reports one time for multi-group test records on the PC
21  Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
22  Compare excitation curves with saved excitation curves in the same window
23  Memory capacity: >1000 groups test results
24  Working condition: temperature: -10℃~50℃; moist: ≤90%

  

   

 


Hot Products

Contact resistance tester HYHL-200A Contact resistance tester output DC 200A current to test the ...
Transformer Load and No-load tester HYKF 1. Measure the transformer load current, load loss, short...
CT PT Analyzer HYVA-402 HYVA-402 can finish: CT/PT volt-ampere characteristic curve test, CT/PT ...
CT PT Analyzer HYVA-402V 1 Turns Ratio, ratio error and phase error test 2 Polarity test for CT 3 ...
CT PT Analyzer HYVA-404 Tests for Current Transformer: 1 Excitation curve and parameters test 2 ...
CT PT Analyzer HYVA-405 Tests for Current Transformer: 1 Excitation curve and parameters test 2 ...