Variable AC Resonance Test System Withstand Voltage for Generator
Test Object and Requirement
The system is specially designed for AC withstand voltage test for
below items, with
below specifications and requirements.
1) AC withstand voltage for 35kV transformer and etc electric
power equipments, test
voltage is not more than 108kV, the frequcy: 45~55Hz, continuous
testing duration
1 minute. Test object capacity ≤0.02uF.
2)AC withstand voltage test for 10.5kV 5000kW generator, test
voltage is not more
than 22kV, test frequency:45~55Hz. Countinous testing duration 1
minute. Test
object capacity ≤0.26uF.
Technical Data
Rated capacity: 108kVA
Input power supply: single phase 220V±10%, 50Hz
Rated voltage: 54kV; 108kV
Rated current: 2A; 1A
Working Frequency: 30-300Hz
Output waveform: sine wave
Waveform distortion rate: ≤1%
Quality factor: Q ≥30 (f=45Hz)
Protective function: Over-current, over-voltage and flashover
protections for test
object.
Temperature rise: ≤65K after constant working of 60mins under rated
load
Accuracy: 1.0% (RMS)
Working time: Constant working of 60mins under rated load. Working
of 1min,
under 1.1 times of rated voltage
More details please contact with sansion power electric, we can
select correctly designed test set for you.
Warranty: One year quality guarantee after shipment.