Home Companies Guangzhou Kingrise Enterprises Co., Ltd.

Two Current Source Single Phase Meter Test Bench 6 - 48 Positions With ICT Class 0.05

Guangzhou Kingrise Enterprises Co., Ltd.

Contact Us

[China] country

Trade Verify

Address: Rm 210,No 69 Guangpu Rd(W), Huangpu Dist. Guangzhou, 510663 CHINA

Contact name:

Inquir Now

Guangzhou Kingrise Enterprises Co., Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Two Current Source Single Phase Meter Test Bench 6 - 48 Positions With ICT Class 0.05

Country/Region china
City & Province guangzhou guangdong
Categories Blowers
InquireNow

Product Details

 Single Phase Electric Meter Test Bench two current source with ICT class 0.05


KE8103 Single Phase Electric Meter Test Bench​ 
 
KE8103 has two current sources, which make it possible to test two elements simultaneously. It is used for testing 1P2W or 3P3W mechanical and electric meter, Number of meter position : 3-48
 
Highlights:

  1. Integrated/Separated aluminum alloy structure, light and reliable, flexible choices
  2. The number of meter positions can be chosen from 6 - 48
  3. Perfect alarming protective function, auto protection of the short circuit ofvoltage,the open circuit of current, and overload.
  4. Full automatic, semi automatic and manual operation available
  5. Supporting bar code input, which increase the efficiency of input
  6. Simultaneous test of the energy meters with same specification, different constants anddifferent classes.
  7. Auto marklocking increases the efficiency of test
  8. Forward and reverse active energy / forward and reverse reactive energy error test
  9. Creeping and starting test
  10. Standard deviation, 24 hour variation test
  11. Influencing quantity test of voltage, frequency, harmonic
  12. Calibration and verification of energy constant
  13. Powerful computer management system, easy and user-friendly
  14. Perfect database management makes the storage, searching, and viewing of the datapossible, and the data can be converted and exported in other forms
  15. The test of open circuit for Neutral voltage (optional)
  16. Adopt multi-serial port system, realizing the parallel communication of computerandthe tested meters (optional)

 
 
Technical specification:
 
 

 

KE8103-10

Number of meter position

10

Accuracy

±0.05%

Voltage output

Output range (P-N)

24V - 300V

Output power of voltage

2 x 250VA

Resolution

Better than ± 0.01%

Stability

Better than ± 0.02% / 150s

Load regulation rate

Better than ± 0.01%

Distortion factor

Better than ± 0.3% (linear resistance load)

Harmonics output

2nd -21st free programmable

Current output

Output range

1mA - 120A

Output power of current

2 x 500VA

Resolution

Better than ± 0.01%

Stability

Better than ± 0.02% / 150s

Load regulation rate

Better than ± 0.01%

Distortion factor

Better than ± 0.3% (linear resistance load)

Harmonics output

2nd -21st free programmable

Phase output

Output range

0 -- 360°

Resolution

± 0.01°

Frequency

Output range

45Hz - 65Hz

Resolution

± 0.01Hz

Operation condition

Power supply

220V±10%,50/60Hz±2Hz

Temperature

-10°C -- +40°C

Humidity

35% -- 85%RH

 
 
 
 Wiring diagram
 

 
 
Packing and shipping
 
 
 

Hot Products

KE8302F IEC standard Energy Meter Test System Accuracy : 0.05 , Used for the test of three phase CT...
KE8301F High Accuracy Energy Meter Testing Equipment Accuracy : 0.05 , Used to test the error of ...
Single Phase Energy Meter Testing Equipment multiple current channels 120A open-link meter KE8102 ...
Energy Meter Testing Bench single phase accuracy 0.05 12 position 120A current KE8101 single phase ...
Single Phase Electric Meter Test Bench two current source with ICT class 0.05 KE8103 Single Phase ...