IEC 12KV 1250A Metal Enclosed Switchgear For Power Plants
 
Scope of useedit
It is widely used in various substations of power systems, power plants, industrial and mining enterprises, and high-voltage power distribution.

Working environment
1. Air temperature: -25℃~+40℃
2. Humidity: Monthly average humidity 95%; Daily average humidity 90% .
3. Altitude: ≤ 2500m
4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
5. No frequent violent shake

Fully type-tested
The switchgear has undergone all the tests required by the international (IEC) Standards. Each switchgear unit is subjected to routine tests in the factory before delivery. These tests are intended to provide a functional check of the switchgear based on the specific characteristics of each installation.

 

Technical data

No.ItemUnitParameter
1Rated voltagekV3.6~24
2Rated frequencyHz50/60
3Rated currentA630,1250,1600,2000,2500,3150,4000
4Branch busbar Rated current630,1250,1600,2000,2500,3150,4000
5Main busbar Rated current630,1250,1600,2000,2500,3150,4000
6

1min Power frequency

withstand voltage

wetKV3850/60
dry4860/65
7Lightning impulse withstand voltagekV7595/125
8Rated short circuit breaking current (peak)KA40/50/63/80/100
9Short time withstand current(4s)20/25/31.5/40
10Protection type IP4X for housing

 

"Five Preventions" of High Voltage Switchgear
 
1. After the vacuum circuit breaker trolley in the high voltage switch cabinet is closed at the test position, the trolley circuit breaker cannot enter the working position. (Prevent closing with load)
 
2. When the grounding knife in the high-voltage switch cabinet is in the closed position, the trolley circuit breaker cannot be closed. (Prevent closing with ground wire)
 
3. When the vacuum circuit breaker in the high-voltage switch cabinet is closing, the back door of the cabinet should be locked with the machine on the grounding knife. (Prevent the electrified interval by mistake).
 
4. The vacuum circuit breaker in the high-voltage switchgear is closed when it is working, and the grounding knife cannot be turned on. (Prevent the live ground wire from hanging)
 
5. The vacuum circuit breaker in the high-voltage switch cabinet cannot exit the working position of the trolley circuit breaker when it is working and closed. (Prevent load broach)

Hot Products

LV DC Distribution Panel 200AH 150AH Metal Enclosed Switchgear DC Panel Power Supply Capacity:40 65 ...
MNS 660V lighting control panel MCC switchgear IP40 CCC ISO9001 GB7251 IEC439 MNS type low voltage ...
630A 3.6KV Metal Enclosed Switchgear KYN28A-12 MV Switchgear Panel General Equipped with VS1 (ZN63) ...
KYN28A-12 Lv Switch Panel 6KV Withdrawable Switchgear General KYN28A-12 is a relatively common high...
IEC 12KV 1250A Metal Enclosed Switchgear For Power Plants Scope of useedit It is widely used in ...
ISO9001 GGJ Low Voltage Main Distribution Panel LV Switchgear Panel GGJ type low voltage switchgear ...