Home Companies Knkong Electric Co.,Ltd

12KV Solid Sealed Pole VCB Circuit Breaker 25KA Explosion Proof

Knkong Electric Co.,Ltd
Active Member

Contact Us

[China] country

Address: No. 25 Street , Hanghai Road, Zhengzhou,Henan,China

Contact name:Ken Chan (English)

Inquir Now

Knkong Electric Co.,Ltd

12KV Solid Sealed Pole VCB Circuit Breaker 25KA Explosion Proof

Country/Region china
City & Province zhengzhou henan
Categories Other Chargers
InquireNow

Product Details

Solid sealed pole vacuum circuit breaker 12KV for indoor electric panel

Voltage: 12-24KV

Current: Max 2000A

Breaking current: 20KA

Type: withdrawable/Fixed

 

Product overview

Vacuum circuit breaker: It is a new type of high-voltage circuit breaker developed in the 1960s (for example, the picture at the beginning of this article is ZN28-12 indoor high-voltage vacuum circuit breaker), which uses vacuum to extinguish arcs. Its advantages are small size, light weight, fast action, fireproof and explosion-proof, low noise and so on. At present, there is a trend to replace other circuit breakers, mainly used in substations below 35KV and places requiring frequent operations in industrial and mining enterprises.

 

Technical Parameters

No.ItemUnitParameter
1Rated voltageKV12
2Rated frequencyHz50/60
3

 

Rated insulation level

1min power frequency withstand voltage(r. m. s)

 

KV

42(phase-to-phase, phase-to-earth)

48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase, phase-to-earth)

85(across the isolating distance)

 

 

4

 

 

Rated current

 

 

A

63063012501600
1250125016002000
  20002500
  25003150
   4000
5Rated short-circuit breaking current

 

KA

202531.540
6Rated short-time withstand current202531.540
7Rated short-circuit marking current506380100
8Rated peak withstand current506380100
9Rated duration of short-circuit    s4
10Rated operating sequence O-0.3s-O/C-180s-O/C
11Breaking times of rated short-circuit currentTimes30/20 times(40KA)
12Mechanical enduranceOps20000
13Rated single capacitor bank breaking current

 

A

630
14Rated back-to-back capacitor bank breaking current400
15Double-earth fault breaking current27.4
16Allowable maximum contact erosion

 

mm

3
17Clearance between open contacts10±1
18Over stroke3.5±0.5
19Non-simultaneity of 3-phase opening and closing

ms

 

≤2
20Bounce duration of contact closing≤2
21Average breaking speed (instant breaking 6mm)

m/s

 

1.1±0.2
22Average making speed0.8±0.2
23Making time

ms

 

≤100
24Breaking time≤50

 

 

25

 

Resistance of each phase main circuit

 

μ Ω

630A≤50
1250A≤45
1600A~2000A≤35
≥2500A≤25
26Contact breaking bounce amplitudemm≤2

 

27

Rated operating voltageRated operating voltage(V)AC/DC

 

V

24*110220
Scope of normal operation voltageOpening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
28Rated voltage of energy storage motorVAC110/220,DC110/220
29Energy storage timeS≤15

 

 

 

Hot Products

VCB 12KV 630A VS1 series vacuum circuit breaker withdrawable type Voltage: 12KV Current: 630A ...
VCB 12KV 630A 1250A 1600A 2000A Vacuum circuit breaker high stability Voltage: 12KV Current: 630A ...
VS1-12 embedded pole Vacuum circuit breaker ODM Voltage: 12-24KV Current: 630-2000A Breaking current...
VS1 series Withdrawable Solid sealed pole VCB vacuum circuit breaker 20KA breaking Voltage: 12KV-24 ...
Solid sealed pole vacuum circuit breaker 12KV for indoor electric panel Voltage: 12-24KV Current: ...
Fixed type indoor panel use 24KV vacuum circuit breaker 310mm phase spacing Voltage: 12-24KV Current...