Knkong Electric Co.,Ltd |
|
Product Introduction
Working condition:
1. Altitude2000m
2. Ambient temperature: -25~50℃
3. Humidity: smaller than 85%
4. After the power cut off, reputing when make sure the remain
voltage is smaller than 10% of the rated voltage, usually this time
is 200s, so the controller you use should has the function of time
delay for reputing after cut off.
Technical :
1. Rated voltage: 230VAC, 400VAC, 525VAC, 690VAC, 750VAC, 1050VAC,
1200VAC
2. Rated output: 1-60 KVAR
3. Rated frequency: 50Hz or 60Hz
4. Capacitance Tolerance: -5% - +10%
5. Tangent of the loss angle: With the power frequency rated
voltage,
6. Withstand voltage: Between terminal 2.15 times rated voltage for
5 seconds, between terminals and container 2 Un+2Kv or 3KVAC choose
the higher one for 10 seconds.
7. Max permissible over-voltage: 110% rated voltage
8. Max permissible over-current: 130% rated current
9. Self-discharge feature: Less than 50V in 3min after power broke
down when the DC is√2 Un as before increased by the capacitors.
10. Applicable standard: GB/T 12747-2004, IEC60831-2002
Model BSMJ BCMJ BZMJ | Rated Voltage(kV) | Rated Output (kvar) | Rated Capacitor(uF) | Rated Current(A) | Hmm) | Output Terminal | Shell Type |
0.4-1-3 | 0.4 |