LW36kV Outdoor SF6 Circuit Breaker High Voltage Switchgear Disconnector

Country/Region china
City & Province shanxi
Categories Other Roadway Products
InquireNow

Product Details

1.LW36kV SF6 HV Overload Switch Circuit Breaker Load Switch

 

LW36-126/T3150-40 outdoor high voltage SF6 circuit breaker uses SF6 as the insulating arc extinguishing medium. It can connect, transmit and disconnect the normal circuit current in the high voltage transmission line; It can also operate the short circuit current or overload current of switchgear. Its structure adopts porcelain type, which can carry out the operation of three-phase opening and closing and automatic reclosing. It can protect and control the transmission line in the 50Hz and 126kV line.
The circuit breaker adopts self-extinguishing principle and is equipped with spring mechanism. When the circuit breaker gets the break command, the rigid parts are moved down by the cylinder, the active arc contact, and the rod under the action of the break spring. When moving, the main fixed contact leaves the active main contact, and the electric current moves to the arc contact, and the arc contact leaves, and an arc appears between the fixed contact and the active contact. When it breaks off the short current, the high capacity current causes a lot of energy between the arc contacts, and the hot gas flows into the thermal expansion chamber, where heat energy is exchanged, and the gas becomes low temperature and high pressure. Now, because the pressure in the thermal expansion chamber is greater than that in the auxiliary chamber, close the check valve of the interrupter. When the current value is zero, the high-pressure gas in the thermal expansion chamber blows back to the gap, and the arc goes out. When it breaks a small current (less than a few thousand amperes), due to low energy, the rising speed of gas pressure in the expansion chamber is slower than the auxiliary chamber, the check valve opens, the compressed gas blows into the expansion chamber, the gas flows, when the current value is zero, the arc goes out.

 

2.Main features:


1.Adopt self-extinguish principle, small operating energy, light mechanical impact;
2.Use spring mechanism, its performance is not relevant to temperature, stable performance;
3.Optimized interrupter structure and movement curve of contact, high reliability on breaking current;
4.Reignite and restrike cannot occur under breaking capacitive current;
5.Optimized pole and frame design with higher capability to endure earthquake;
6.High reliability, long average normal service time, low maintenance cost;
7.Convenient installation and configuration in field, it takes only one day or two days;

 

3.Technical parameters

 

NO.ltemsUnitParameter
1Rated voltageKV126
2

Rated power frequency withstand

voltage(1min)

Phase-to-phase

Phase-to-ground

KV230
fractureKV230+73*
3

Rated lightning impulse withstand

voltage

Phase-to-phase

Phase-1o-ground

KV550
fractureKV550+103*
4

Power frequency withstand voltage ( 5min ) under SF6

zero-gauge pressure

kV95
5Rated frequencyHz50
6

Rated current

Raled short circuit breaking current

A3150
7kA40
8First-pole-to-clear factor 1.5
9Rated short circuit making current(DC component) More than 41%
10Rated short circuit making current(peak)kA100
11Rated short time withstand current(ms)kA40
12Rated short time withstand currentkA100
13Rated short circuit durations4
14Rated out-of phase breaking currentkA3(OP1),10(OP2)
15Short range breaking currentkA36;30
16Wrong-phase earthing breaking currentkA34.8
17Rated line charging switching currentA31.5
18Full capacity breaking time without check and repairTimes

20 or rated current breaking

times:3000

19Rated operating sequence O-0. 3s-CO-180s-CO
 
4.Environmental conditions:
 
Installation siteoutdoor
Ambient temperature-25℃~+40℃
Max. daily temperature difference≤25℃
Height above sea level2000m(no limit for specified order)
Air humidityDaily average:≤95%;
month average:≤90%;
Wind speed≤34m/s
Solar radiation≤0.1W/cm2(fine day, noon)
Earthquake intensityhorizontal:≤0.3g;vertical:≤0.15g
Icing thickness≤10mm
Creepage distance25mm/kV or 31mm/kV
Static load on terminal in Y-direction1250N
Static load on terminal in X-direction750N
Static load on terminal in Z-direction1000N

 

5. FAQ

 

1. All our activities are accredited to ISO 14001:2015 and IEC standard.

2. Technology ensure the quality satisfy international request.

3.Generally we promise one - two years quality guarantee, some products will be extended longer time for life span.

4. For tender cooperation, it is welcome to discuss the detail in between.

Hot Products

1. AC Power Distribution Switchgear 40.5kv 33kv High Voltage Power Distribution Switchgear is a ...
1. 7.2kV 12kV 17.5kV LV Low Voltage Switchgear For Ac Power Grids LV Low Voltage Switchgear is used ...
Indoor LV Power Distribution Switchgear 24kV 36kV 40.5kV Power Distribution Switchgear is widely ...
1. 33kv 40.5KV Electrical Distribution Switchgear GB3906 Standard Electrical Distribution Switchgear ...
1.LW36kV SF6 HV Overload Switch Circuit Breaker Load Switch LW36-126/T3150-40 outdoor high voltage ...
1.LW8-40.5 SF6 Heavy Duty High Voltage Circuit Breaker Lw8-40.5 product has excellent crushing ...