Home Companies Zhejiang Hengrui Technology Co., Ltd.

150AH Telecom Battery Safety Installation High Discharge Rate Enviroment Friendly

Zhejiang Hengrui Technology Co., Ltd.
Active Member

Contact Us

[China] country

Address: 8F, Building 3, Tianxing International Center, No. 508 Fengtan Road, Hangzhou, China. 310011

Contact name:Yang

Inquir Now

Zhejiang Hengrui Technology Co., Ltd.

150AH Telecom Battery Safety Installation High Discharge Rate Enviroment Friendly

Country/Region china
City & Province hangzhou zhejiang
Categories Batteries
InquireNow

Product Details

  • 12 V 150AH Lead-acid Batteries with Long Life of 12 Floating Charging Conditions,L558mm x W112mm x H295mm
  • Product Overview

          The HRESYS DF (Duration Front) series VRLA batteries is especially designed for telecommunication

          with 12+ years float design life. By combining the newly developed paste formula with up-to-date AGM

          structures, the series meet latest IEC, British and Telcordia standards. Front Access connection and

          centralized venting system of DF series for fast, safety installation and maintenance.

 

  • Features and Benefits​

          - 12+ years long life design at float condition
          - International Standards Compliance, i.e. IEC, EN, BS, CE etc.
          - Batteries are mainly working at standby status but also for cyclic use with not very frequent cycles
          - Depth of Discharge shall normally not exceed 60% when it is used in cyclic scenarios
          - Long cycle life thanks to thick plates with Tin Calcium alloy
          - Low self-discharge rate enables long shelf life

 

  • Applications

 

  • Management and Product Certificates

          -ISO9001:2015

          -ISO14001:2015

          -OHSAS18001:2007

          -CE Certificate

 

  • Product Specification​
Nominal Voltage (V)12 (6 cells per unit)
Nominal Capacity (25 C)150 Ah @ 10HR-rate (to 1.80Vpc)
Dimension (mm)L558mm x W112mm x H295mm
Approx. Weight45.3 kg (99.9 lbs)
Terminal TypeFemale Copper Insert M8 (torque: 10~12N.m)
Internal ResistanceApprox. 0.005 Ohm (fully charged)
Max. Charge Current37.5 A
Max. Discharge Current (5S)900 A
Short Circuit Current2400 A
Self DischargeApprox. 2.5% per month @ 20℃
Ambient TemperatureDischarge: -20~60℃
Charge: -20~55℃
Storage: -20~45℃
Float Charge Voltage13.5V/block @25℃(-3mV/ cell/ C)
Сycle Use Charge Voltage14.1V/block @25℃
Container MaterialABS UL ( 94-V0 optional)

 

 

  • Battery Dimension

 

  • Performance Curves

 

  • Factory Overview

 

 

 

 

Hot Products

2 V 150 AH Tubular Gel Batteries for Renewable energy application , L103mm x W206mm x H390mm Product ...
12 V 170AH Lead-acid Batteries with Long Life of 12 Floating Charging Conditions,L560mm x W125mm x ...
12 V 160AH Lead-acid Batteries with Long Life of 12 Floating Charging Conditions,L560mm x W125mm x ...
12 V 150AH Lead-acid Batteries with Long Life of 12 Floating Charging Conditions,L558mm x W112mm x ...
OPZV12-60 12V Tubular Gel Batteryfor Renewable Energy System , L260mm x W170mm x H210mm Product ...
OPzV12-100 12V Tubular Gel Batteryfor Renewable Energy System , L407mm x W175mm x H210mm Product ...