Guangdong Shengyu Cable Industry Co., Ltd. |
|
Single Core AWA Low Smoke Zero Halogen Cable LSZH Power Cables For Network
APPLICATION
Single core LSZH cable with aluminium wire armour (AWA). Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.
CONSTRUCTION
Conductor
Class 2 stranded copper conductor according to BS EN 60228
(previously BS 6360)
Insulation
XLPE (Cross-Linked Polyethylene) Type GP8 according to BS 7655
Bedding
LSZH (Low Smoke Zero Halogen) Type LTS1 according to BS 7655
Armour
AWA (Aluminium Wire Armour)
Sheath
LSZH (Low Smoke Zero Halogen) Type LTS1 according to
BS 7655
STANDARDS
BS 6724, BS EN/IEC 60502-1, BS EN/IEC 60754-1 and 2,BS EN 50267-2-1 and 2, BS EN/IEC 61034-1, BS EN/IEC 60332-1-2, BS EN/IEC 60332-3-24 Cat C
We supply LPCB Certified products
The electrical and dimensional properties of this product are
measured by the Technical and Quality Assurance department at
the Cables laboratory. Cable performance in respect of
conductor resistance, construction quality (workmanship),
dimensional consistency, and other parameters are verified to
published standards and approved product drawings. Conformance to
RoHS (Restriction of the use of Hazardous Substances) is determined
and confirmed
CHARACTERISTICS
Voltage Rating
600/1000V
Temperature Rating
Fixed installation: -20°C to +90°C
Minimum Bending Radius
1.5mm2 to 16mm2 - Fixed: 6 x overall diameter
25mm2 and above - Fixed: 8 x overall diameter
Core Identification
1 core: Brown
Sheath Colour
Red
Ambient temperature: 30ºC
Conductor operating temperature: 90ºC
Notes
1. Where a conductor operates at a temperature exceeding 70ºC it
must be ascertained that the equipment connected to the conductor
is suitable for the conductor operating
temperature (see Regulation 512.1.2 of the 17th Edition of IEE
Wiring Regulations).
2. Where cables in this table are connected to equipment or
accessories designed to operate at a temperature not exceeding 70ºC
, the current ratings given in the equivalent
table for 70ºC thermoplastic insulated cables (Table 4D3A) must be
used (see Regulation 523.1 of the 17th Edition of IEE Wiring
Regulations).
The above table is in accordance with Table 4E3A of the 17th