 AC Input to UPS

A.    Voltage Configuration: The UPS shall incorporate a variable input voltage window feature that shall operate at the values in the following table, without drawing power from the batteries.

Load Level

500-1000 VA

120 VAC

Input Voltage

1500-3000 VA

120 VAC

Input Voltage

3000 VA

208 VAC

Input Voltage

700-2000 VA

230 VAC

Input Voltage

3000 VA

230 VAC

Input Voltage

100%

90 VAC

102 VAC

177 VAC

177 VAC

196 VAC

90%

86 VAC

96 VAC

168 VAC

168 VAC

184 VAC

80%

81 VAC

90 VAC

159 VAC

159 VAC

173 VAC

70%

77 VAC

84 VAC

150 VAC

150 VAC

161 VAC

60%

73 VAC

78 VAC

142 VAC

142 VAC

150 VAC

50%

69 VAC

72 VAC

133 VAC

133 VAC

138 VAC

40%

64 VAC

66 VAC

124 VAC

124 VAC

127 VAC

30%

60 VAC

60 VAC

115 VAC

115 VAC

115 VAC

B.     Frequency:UPS shall auto-sense input frequency when first powered up and shall operate within the following frequency specifications. UPS shall be capable of cold start with default frequency of 60Hz (120VAC and 208VAC units) and 50Hz (230VAC units). Once started the frequency operating window shall be 40-70Hz.

 

Three frequency settings shall be available in the Liebert GXT4 Configuration program: Auto frequency sensing (factory default setting), 50Hz frequency conversion and 60Hz frequency conversion.

C.    Input Power Factor:>0.99 lagging at rated load.

D.    Input Current reflected distortion: 5% THD typical.

E.     Input Current Ratings

UPS Model #

120VAC Units

230VAC Units

208VAC Units

500RT

4.2A

N/A

N/A

700RT

5.8A

2.9A

N/A

1000RT

8.3A

3.9A

N/A

1500RT

12A

5.9A

N/A

2000RT

16A

7.8A

N/A

3000RT

24A

11.7A

N/A

3000RT208

N/A

N/A

12.9A


F.     Inrush Current (initial startup, no load): The UPS shall have a maximum inrush current of 6 times the full load peak input current.

G.    Input Line Transient Immunity: UPS shall conform to an input line transient conforming to IEEE C62.41, Category A, Level 3 tests for 120VAC and 208VAC models. The 230VAC models shall meet EN61000-4-5.

H.  Surge Protection

·         120VAC units:  MOV ratings shall be 175V, 80 Joules minimum connected L-N.

·         208VAC units:  MOV ratings shall be 320V, 80 Joules minimum connected L1-L2, L1-G and L2-G.

·         230VAC units:  MOV ratings shall be 320V, 80 Joules minimum connected L-N.

1.1.1.2    AC Output, UPS Inverter

A.  Voltage Configuration

·         120V units:     120VAC, 50/60Hz, single-phase, 2-wire-plus-ground, configuration program selectable (110V, 115V, 120V, 127V).

·         208V units:     208VAC, 50/60Hz, single-phase, 2-wire-plus-ground, configuration program selectable (208V, 220V, 230V, 240V).

·         230V units:     230VAC, 50/60Hz, single-phase, 2-wire-plus-earth, configuration program selectable (220V, 230V, 240V).

B.     Voltage Regulation

± 3% steady state.

C.    Frequency Regulation

 ±5% synchronized to utility / mains. ±0.1Hz free running or on-battery operation.

D.    Frequency Slew Rate

 1.0Hz per second maximum

E.   Voltage Distortion

<3% total harmonic distortion (THD) typical into a 100% linear load, <5% THD typical into a 100% non-linear load with crest factor ratio of 3:1.

F.     LoadPowerFactorRange

The load power factor range shall be 0.65 lagging to 1.0 (unity) without power derating.

G.    Output Power Rating

Output power rating shall be 500VA/450 Watts, 700VA/630 Watts, 1000VA/900 Watts, 1500VA/1350 Watts, 2000VA/1800 Watts and 3000VA/2700 Watts at 0.9 lagging power factor.

H.  Inverter Overload Capability

 

500VA - 2000VA

3000VA

120V / 208V

105% to 125% - 60 seconds

105% to 125% - 15 seconds

125% to 150% - 50 seconds

125% to 150% - 10 seconds

150% to 200% - 2 seconds

150% to 200% - 2 seconds

>200% - 250ms

>200% - 250ms

230V

105% to 125% - 60 seconds

105% to 125% - 55 seconds

125% to 150% - 50 seconds

125% to 150% - 55 seconds

150% to 200% - 2 seconds

150% to 200% - 2 seconds

>200% - 250ms

>200% - 250ms

I.       Voltage Transient Response

·        ±7% in line mode 0-100-0 % loading of the UPS

·        ±7% in battery mode for 0-100-0% loading of the UPS rating.


J.      Transient Recovery Time

 To nominal voltage within 90 milliseconds.

K.  AC-AC Efficiency:

The 700VA-3000VA 120V; 3000VA 208V; and 700-3000VA 230V UPS models shall be EPA ENERGY STAR qualified and labeled

·         500RT120: 88% AC –AC at full rated linear load

·         700RT120: 89% AC –AC at full rated linear load

·         1000RT120: 88% AC –AC at full rated linear load

·         1500RT120: 89% AC –AC at full rated linear load

·         2000RT120: 89% AC –AC at full rated linear load

·         3000RT120: 89% AC –AC at full rated linear load

·         3000RT208: 90% AC –AC at full rated linear load

·         700RT230: 89% AC –AC at full rated linear load

·         1000RT230: 89% AC –AC at full rated linear load

·         1500RT230: 90% AC –AC at full rated linear load

·         2000RT230: 91% AC –AC at full rated linear load

·         3000RT230: 90% AC –AC at full rated linear load

L.   Programmable & Controllable Outlets:

The UPS units shall have 2 groups of programmable and controllable outlets.  These shall be user customizable to program to perform load shedding based upon battery capacity remaining, time on battery operation, battery time remaining, and overload condition when on battery power.  The user shall also be able to program these groups for sequential restart of connected equipment based upon time after input power is restored.  The user can also program these to always be turned off to prevent unauthorized equipment from being plugged into the UPS.


1.2        ENVIRONMENTAL CONDITIONS

A.  Ambient Temperature

Operating: The ambient temperature range, when UPS is operational, shall be from 32°F to 77°F (0°C to 25°C). There shall not be any degradation in the performance when operating in this range. Automatic derating shall occur for operation in higher ambient temperatures based on the following table.

Ambient Temperature

78-86°F ±5°F
(26-30°C ±3°C)

87-95°F ±5°F
(31-35°C ±3°C)

96-104°F ±5°F
(36-40°C ±3°C)

Max Output Power Factor degradation @ max load

100%-93%

92%-86%

85%-79%


Storage: 5°F to 122°F (-15°C to 50°C )

B.  Relative Humidity

Operating: 0 to 95% non-condensing.

Storage:     0 to 95% non-condensing.

C.  Altitude

10,000 ft. (3,000m) max without power derating when operated within the temperature specified in Section 1.4, Item A. Ambient temperature shall be derated 9°F (5°C) for each additional 1600 ft. (500m) above 10,000 ft. (3,000m).

Packaging & Shipping

 

Our Services

100% Low Price Guarantee:
 Uonel provides high-quality products at low wholesale prices
100% Quality Assurance:
All items are ORIGINAL NEW  and GENUINE only.
Free  Technical Support:

Our FREE Huawei Expert Consultancy Support is over the phone, by chat, by email or by login remotely.

100% Money Back Guarantee:
You can contact our customer service team to exchange or return any product that you bought from us.

Flexible Secure Payment & Shipment:
Verified authorization: Mcafee Secure, VeriSign Secured

Company Information

Uonel is one of the biggest Cisco&Huawei Network Hardware distributor in china, founded in 2008. We are a global provider of netwotking  products with more than 5000 customers.

We provide original new Huawei&Cisco Routers,Switches,Firewalls,Wireless APs & controllers,OLTs,GPON modems,optical transceivers.Our company have more than $5million Huawei&Cisco products in stock.

Most of our technical engineers had work exprience in Huawei company,we can provide network design&planning,configration,troubleshooting,maintenance and training service in world wide.

 

 
 
 
 














Hot Products

UONEL CO LIMITED Contact person:Natasha Mobile/Whatsapp/Skype/Wechat:+86 13798264392 Website:www...
UONEL CO LIMITED Contact person:Natasha Mobile/Whatsapp/Skype/Wechat:+86 13798264392 Website:www...
UONEL CO LIMITED Contact person:Natasha Mobile/Whatsapp/Skype/Wechat:+86 13798264392 Website:www...
UONEL CO LIMITED Contact person:Natasha Mobile/Whatsapp/Skype/Wechat:+86 13798264392 Website:www...
UONEL CO LIMITED Contact person:Natasha Mobile/Whatsapp/Skype/Wechat:+86 13798264392 Website:www...
UONEL CO LIMITED Contact person:Natasha Mobile/Whatsapp/Skype/Wechat:+86 13798264392 Website:www...