1. Product Name:

Primary Current Injection Test System SLQ

 

2. Equipment Description:

​SLQ primary injection test set is a high current generator instrument. It is applied in current transformer test , circuit breaker test and so on. Adjustable output current, smooth in current rise, large scope of load variation, easy and safe operation.

 

3.Technical Parameters:

Type

Capacity

(kva)

Power supply

Output

Impedance voltage  %

Idle current  %

mode

I

(A)

V

(V)

I

(A)

V

(V)

SLQ-5/500

3

13.6

220

500

5

>8

>6

single

SLQ -5/1000

5

22.7

220

1000

5

>8

>6

single

SLQ -10/2000

10

46

220

2000

5

>8

>6

Separated

SLQ -12/4000

12

30

400

2000/4000

6/3

>8

>6

Separated

SLQ -15/5000

15

37.5

400

2500/5000

6/3

>8

>6

Separated

SLQ -150/25kA

150

375

400

25000

6

>8

>6

Separated

 

Environment temperature: 0~50°C

Humidity: ≤85%RH

 

4. Safety Warnings
1) The test set must be connected to earth reliably before use
2) The output terminals should be clean before switching on
3) The test set should be in power off before make connections for the test
4) After the high current output the metal terminals are very hot. It is forbid to touch those parts
5) It is forbid to touch the terminals or high current circuit when test set is switched to ON position
6) The duty cycle should not be exceeded
7) Any replacement should be made when test set is switched off
8) The test set should never be connected to the live power line

 

5. The SLQ primary injection tester has two kinds of model. One is integral box and another is the separated box. The model is depends on the maximum capacity output of the whole tester. If the
whole capacity of the tester is less or equal to 5KVA, the control unit and the current booster will
be designed in one single box. Otherwise the control unit will be a one box and the current booster will be a one box.

Hot Products

Basically Model Primary Current Injection Test Set Signal Phase 500A - 2000A 1. Product Name: ...
Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance 1. Product ...
Substation Maintenance Primary Current Injection Test Set AC220V Or AC 400V 1. Product Name: Primary ...
Automated Short Time Thermal High Current Test Equipment AC380V 45Hz - 65Hz 1 Summary Automated ...
Current load Primary Current Injection Test Set 1000A 220V Single Mode 1. Product Name: Primary ...
Auto Transformer Adjustable Primary Current Injection Test Kit For Circuit Breaker Measurement 1. ...