Power Transformer On-load Tap-changer Characteristics Tester , Transformer Tap-changer Tester

 

I. Products Description and Application 

 

FKC-1A Tester is a comprehensive test equipment which is used to measure and analyze electrical properties index of on-load tap-changer of power transformer and special transformer in power system and has the function of analyzing, saving and printing test data. Controlled by computer, it can realize auto measuring of parameters such as transition time, transition waveform, transition resistance, and three-phase synchronism of on-load tap-changer through specially designed measuring circuit, so that user can not only measure via tap-changer lead, but also carry out measuring through direct wiring of three-phase sleeve of transformer and neutral point according to needs and site condition.

 

FKC-1A  Tester is of vital importance in improving reliability of power system operation when promptly diagnosing latent fault of tap-changer in preventive test of power equipment and transformer overhaul, solving the problems of test method of on-load tap-changer of power transformer outdated and undedicated.

 

 

II. Features

 

1. Three-way independent test power source,  max output current being 0.5A 1A

2. Equipment sample rate:  10~20 KHZ

3. Max saving time of single waveform: 6.4 seconds

4. Measuring range of transition resistance:1-40Ω  for Y/0 type transformer

                                                                      1-20Ω  for Y type transformer.

5. Measuring accuracy:1-5Ω,≤±10%.

                                      5-40Ω,Δ≤±5% Time error:Δ≤±1%

6. Monitor:240´128T, T6963C controller

7. Processing part:high speed 8-bit micro-processor, data memory: 512K

8. High speed A/D converter, max sample rate being 400 KHZ

9. Power source :220V ±10% Power £200W

10. Dimension: 410mm´320mm ´200mm.

11. Weight :20kg

 

 

III. Accessories

  • Test clip with 10m testing wire       4 pieces
  • Alligator clip with 1m testing wire   4 pieces
  • Power line                                     1 piece
  • Printing paper                               2 rolls

 

Hot Products

Insulation Resistance Tester for Water-cooled Type Power Generator Product Introduction : Model ...
Digital Insulation Resistance Test Set for Power Transformer , Portable 10kv Megger Insulation ...
Power Transformer No-load And On-load Loss Characteristics Tester , Transformer Load Loss Tester I. ...
Power Transformer Capacity Characteristic Tester , Measure The Capacity Of Distribution Transformers ...
Power Transformer On-load Tap-changer Characteristics Tester , Transformer Tap-changer Tester I. ...
Automatic Insulation Oil BDV Tester , Transformer Oil Dielectric Strength Testing machine I. ...