Variable Frequency Resonant Withstand Voltage Test Set , For EHV High Voltage GIS Test

 

I. Application :


This test set model CHX-4800KVA/200KV,400KV,600KV,800KV is designed to perform on-site AC hipot test with variable frequency resonant circuit technology for above 110kV~800KV class GIS and other HV electrical facilities ; The highest test voltage is no more than 200KV,400KV,600KV or 800KV through modular HV test reactors in parallel or in series connection ;the test frequency can be from 30-300Hz; the duty cycle is no more than 15mints or 60mints.

 

Through modular test reactors is connected in parallel or in seires, the test set also can be performed the following on-site AC hipot test:

1.1 No more than 200KV and 24A for HV GIS  with no more than Urated=123KV and other HV electrical facilities

1.2 No more than 400KV and 12A for HV GIS with no more than Urated=300KV and other HV electrical facilities

1.3 No more than 600KV and 6A for EHV GIS with no more than Urated=550KV and other HV electrical facilities

1.4 No more than 800KV and 6A for EHV GIS with no more than Urated=800KV and other HV electrical facilities

 

Until now , we had supplied 1200KV and 9A rariable frequency resonant test system for China power grid company.  The designed test set also forms many different serialized model according to different HV or UHV withstand test applications through test reactors in series or in parallel connection and number of configurations in each set, The alike model can see other typical model at following clause.


II. Main Components:

 

SNName of ComponentsType and specificationQty.Each weightEach Dimension 
1Variable frequency powerFKVF-200kW/380V1piece180kgs750*700*1000mm
2Excitation transformerCQSB(J)-200kVA1piece1800kgs650*650*800mm
3HV resonant test reactorCHX(kf)-1200kVA/200kV4pieces2800kgsD1200*H1250mm
4Capacitive dividerTRF-800kV/1000pF1set550kgsD350*H7600mm
5Special test accessories 1set  

 

 

 

 

 

 

 

 

Note:1. Load capacitantor can be optional when small load line is tesing or need analog load to control test frequency .

2. Test reactor can be produced to be 150KV,200KV,250KV,300KV, 350KV, 400KV for each piece rated voltage according to different tested object scope or customer requried. The max. rated current of each HV reactor can be 1~15A optional in this serialized set, 

3.  HV Damping inductance can be optional for suppressing  high frequency harmonics and resisting  overvoltage caused from tested object flashover, special in EHV or UHV test set.

 

III. Test priciple :
Portable Variable Frequency Resonant Withstand Voltage Test Set

VF: Variable Frequency Power Source T : Excitation Transformer
L : Test Reactor Cx: Tested Equipment MOA1: Lightning Arrestor
C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm )


IV. General Technical Data:

  1. Mode of system test: Series resonant with variable frequency
  2. System model : CHX-4800KVA/200KV,400KV,600KV, 800KV
  3. Input power supply : 380±10%(three-phase),50Hz/60Hz
  4. Number of HV test reactor: 4pieces
  5. Rated output capacity: 4800kVA
  6. Rated output Voltage: 200KV,400KV,600KV,800KV
  7. Max Test voltage : no more than 200KV,400KV,600KV,800KV
  8. Rated output current: 6A /single piece or in series;12A or 24A in parallal
  9. Reg. Freq range : 30Hz-300Hz
  10. Output Resonance voltage waveform: sine wave
  11. THD of output waveform: ≤1%
  12. Insulation level: Under 1.1 times and keeping 1min, normal
  13. Duty cycle : 15mins or 60mints optional on under rated current working condition ;
  14. Quality factor of test set itself: Q≥60
  15. Temperature rise: Less than 65K under rated current working withn duty cycle;
  16. Noise level: No more than 70B
  17. Reactor Structure: oil immersed type, epoxy tube cylinder type;


V.Main Measuring and control software panel as following :


Portable Variable Frequency Resonant Withstand Voltage Test Set


VI.Accessories

  • Accessory box for storage accessoires
  • Input cables of power source
  • Output cables of power source
  • Output cables of exciting transformer
  • System grounding cables
  • Parallel cables of the reactor
  • HV measuring cables ( the signal output cables of voltage divider )
  • HV output cables(reactor to divide,divider to test object)
  • Supporting base for divider
  • Corona ring for test reactor and divider
  • A final test report, a quality Certificate ,a user manual and a packing list are offered .


VII. Other Typical Model

 

7.1 For 123KV ~300KV  class GIS on-site AC hipot test

 

ModelRated voltageRated output currentRated output capacity

Application

(From 45Hz starting)

CHX-400KVA/200KV,400KV200KV*22A@200KV400KVAFor 123KV and below class GIS
1A@400KVFor 300KV and below class GIS
CHX-800KVA/200KV,400KV200KV*24A@200KV800KVAFor 123KV and below class GIS
2A@400KVFor 300KV and below class GIS
CHX-1000KVA/200KV,400KV200KV*25A@200KV1000KVAFor 123KV and below class GIS
2.5A@400KVFor 300KV and below class GIS
CHX-2000KVA/200KV,400KV200KV*210A@200KV2000KVAFor 123KV and below class GIS
5A@400KVFor 300KV and below class GIS
Special requirement can be made by order

 

7.2 For 145KV ~362KV class GIS on-site AC hipot test

 

ModelRated voltageRated output currentRated output capacity

Application

(From 45Hz starting)

CHX-500KVA/250KV,500KV250KV*22A@250KV500KVAFor 145KV and below class GIS
1A@500KVFor 362KV and below class GIS
CHX-1000KVA/250KV,500KV250KV*24A@250KV1000KVAFor 145KV and below class GIS
2A@500KVFor 362KV and below class GIS
CHX-2000KVA/250KV,500KV250KV*28A@250KV2000KVAFor 145KV and below class GIS
4A@500KVFor 362KV and below class GIS
CHX-3000KVA/250KV,500KV250KV*212A@250KV3000KVAFor 145KV and below class GIS
6A@500KVFor 362KV and below class GIS
Special requirement can be made by order


7.3 For 170KV ~550KV class GIS on-site AC hipot test

 

ModelRated voltageRated output currentRated output capacity

Application

(From 45Hz starting)

CHX-1200KVA/300KV,600KV300KV*24A@300KV1200KVAFor 170KV and below class GIS
2A@600KVFor 550KV and below class GIS
CHX-1800KVA/300KV,600KV300KV*26A@300KV1800KVAFor 170KV and below class GIS
3A@600KVFor 550KV and below class GIS
CHX-2400KVA/300KV,600KV300KV*28A@300KV2400KVAFor 170KV and below class GIS
4A@600KVFor 550KV and below class GIS
CHX-3600KVA/300KV,600KV300KV*212A@300KV3600KVAFor 170KV and below class GIS
6A@600KVFor 550KV and below class GIS
CHX-4800KVA/300KV,600KV300KV*216A@300KV4800KVAFor 170KV and below class GIS
8A@600KVFor 550KV and below class GIS
Special requirement can be made by order

 


7.4 For 123KV ~800KV class GIS on-site AC hipot test

 

ModelRated voltageRated output currentRated output capacity

Application

(From 45Hz starting)

CHX-2400KVA/200KV×4800KV12A@200KV2400KVAFor 123KV and below class GIS
6A@400KVFor 300KV and below class GIS
3A@600KVFor 550KV and below class GIS
3A@800KVFor 800KV and below class GIS
CHX-3600KVA/200KV×4800KV13A@200KV3600KVAFor 123KV and below class GIS
9A@400KVFor 300KV and below class GIS
4.5A@600KVFor 550KV and below class GIS
4.5A@800KVFor 800KV and below class GIS
CHX-4800KVA/200KV×4800KV24A@200KV4800KVAFor 123KV and below class GIS
12A@400KVFor 300KV and below class GIS
6A@600KVFor 550KV and below class GIS
6A@800KVFor 800KV and below class GIS
Special requirement can be made by order

 

 

VIII.  On-site insulation test standard table from IEC 62271-203:2011 for HV GIS  

Variable Frequency Resonant Withstand Voltage Test Set for long HV XLPE Cable

Hot Products

Power Frequency AC Resonant Withstand Voltage Test Set , For Thermal Generators Test I. Product ...
Variable Frequency Resonant Withstand Voltage Test Set , Container Type HV Test Set With Resonance , ...
Variable Inductance Resonant Withstand Voltage Test Set , Hydraulic Type HV Test Set With Resonance ...
Variable Frequency Resonant Withstand Voltage Test Reactor For Long HV XLPE Cable I. Application : ...
Variable Frequency Resonant Withstand Voltage Test Set , For EHV High Voltage GIS Test I. Applicatio...
Power Frequency AC Resonant Withstand Voltage Test Set , For EHV CVT and CB Rutine Testing I. ...