AAAC Conductor, All Aluminium Alloy Conductor (ASTM B 399/B 399M)
1. Applications
Conductor(AAAC) have been widely used in power transmission lines
with various voltage levels, and also used in power lines across
great rivers, heavy ice area, and other places special geographical
characteristics. The conductor have excellent advantages of high
strength, large current carrying capacity and good catenary
property as well as wear-resistance, anti-crush and corrosion-proof
with simple structure, convenient installation and maintenance, low
cost for the line, large transmission capacity.
2. Specifications
Conductor(AAAC) bear conductor meets or exceeds the following
Specifications:
ASTM B 399/B 399M
Code | Cross. Section | Stranding & Wire ø | Overall ø | Weight | Rated strength | Electr.resist. at 20ºC |
(mm2) | (Nºx mm) | (mm) | (kg/km) | (KN) | (ohm/km) |
ALTON | 24.70 | 7x2.12 | 6.36 | 68 | 7.84 | 1.3576 |
AMES | 39.30 | 7x2.67 | 8.02 | 108 | 12.40 | 0.8533 |
AZUSA | 62.50 | 7x3.37 | 10.11 | 172 | 19.00 | 0.5364 |
ANAHEIM | 78.70 | 7x3.78 | 11.35 | 217 | 24.00 | 0.4255 |
AMHERST | 99.20 | 7x4.25 | 12.75 | 273 | 30.20 | 0.3379 |
ALLIANCE | 125.10 | 7x4.77 | 14.31 | 345 | 38.10 | 0.2658 |
BUTTE | 158.50 | 19x3.26 | 16.30 | 437 | 46.70 | 0.2114 |
CANTON | 199.90 | 19x3.66 | 18.30 | 551 | 59.00 | 0.1675 |
CAIRO | 235.80 | 19x3.98 | 19.88 | 650 | 69.60 | 0.1421 |
DARIEN | 283.50 | 19x4.36 | 21.79 | 781 | 83.60 | 0.1181 |
ELGIN | 330.60 | 19x4.71 | 23.54 | 911 | 97.50 | 0.1013 |
FLINT | 375.40 | 37x3.59 | 25.16 | 1.035 | 108.00 | 0.0892 |
GREELEY | 469.80 | 37x4.02 | 28.14 | 1.295 | 136.00 | 0.0712 |