200KW-400V Intelligent Stainless Steel Resistor Generator Load Bank

 

Generator load bank testing is an essential part of good maintenance practices. Performing yearly load bank tests helps to extend the generator’s engine life, and ensure reliable operation during a utility power failure.

 

What is generator load bank testing?

 

Load bank testing allows a standby generator to be tested and exercised to verify its overall reliability, and its ability to run at its full rated KW output. Typically, a generator is running at a level far less than the units rated output capability. Load bank checks the engine’s ability to perform and provide the required horsepower when called upon in an emergency. When a load bank is used, the artificial load it provides brings the engine up to an acceptable operating temperature.

 

Key features of the generator load bank:


1. Mobile Dummy Load Bank for generator testing
Mobile design easy for Generator, Electrical and Marines Load Testing;


2. Use low heat created heating element;


3. Continuous operation;


4. Large Load Capacity;


5. Load Step Resolution plus Variable adjustment;


6. Digital Metering.

 

Technical Parameters for reference:

 

System componentsLoad bank, resistive load,data collection, automatic control and manual control, electrical control, cooling devices and auxiliary control,Industrial machines, printer.
Total discharge power200KW
Resistive load stallsstep: 5KW
Test voltageThree-phase AC400V
Test Frequency50Hz
Resistance tubeInsulation resistance of each resistor above DC500V 100MΩ , Pressure AC2000V 1 minute, Resistance to high temperature.
Load connectionStar (three-phase four -wire)
Loading precision±3%;
Work wayContinuous work
Working power480VAC/50Hz/Three-phase four-wire system; (reservation terminals)
Operator terminalIPC / software, full realization of automated control
Control modeManual control / computer software auto control
Measured Control FunctionLoad subtraction control, extended load automatic identification synchronization control
IPC detection functionI, V, HZ, KW, COSΦ etc.Real-time display, electrical performance testing, curves and report output, system electrical parameters monitoring, automatic data acquisition;
Parameter recordForm through EXCEL, curves pictures saved by WORD document
Parameter displaythree-phase voltage, three- phase current, apparent power, active power, reactive power, power factor, frequency, etc.;
Load protectionOvervoltage, overcurrent, high temperature, air flow and fan failure protection;
Fault alarmFan failure, load high temperature alarm
Dimension1100*1300*1400
Weight350kg
Applicable ScopeFor marine diesel generator sets, land diesel generators, power inverters, UPS systems

 

Hot Products

50KW-400V Generator Load Bank to Prevent the Generator Carbon Deposition Main Features of the ...
75KW-400V Power Factor Generator Load bank for Car Generator Testing Main Features: * The load bank ...
Bule Colour 100KW-400V Generator Load Bank with Remote Control Fullde powered load banks solutions ...
150KW-400V Generator Load Bank Unit Injection System Diagnostic Test Our Commitments: * Management ...
200KW-400V Intelligent Stainless Steel Resistor Generator Load Bank Generator load bank testing is ...
Alloy Resistor Rainproof 250KW-400V Generator Load Bank for Generator Testing Multifunctions of the ...