Home Companies China • Yuanda Valve Group Co., Ltd.

Ductile Iron Flange End Water Conservancy Valve Differential Pressure

China • Yuanda Valve Group Co., Ltd.
Active Member

Contact Us

[China] country

Address: Jianshe South Street, Yuhua District, Shijiazhuang City, Hebei Province, China

Contact name:Ada Chen

Inquir Now

China • Yuanda Valve Group Co., Ltd.

Ductile Iron Flange End Water Conservancy Valve Differential Pressure

Country/Region china
City & Province shijiazhuang hebei
Categories Valves
InquireNow

Product Details

Ductile Iron Differential Pressure Bypass Valve Flange End Water Conservancy Valve

 

 

Product introduction

 

800X DIFFERENTIAL BYPASS BALANCING valve is a valve used to balance the pressure difference between supply/return water in air conditioning systems. The valve can improve the utilization of the system, maintain an accurate constant value of the differential pressure, and can minimize the noise of the system, as well as excessive differential pressure damage to the equipment, 800X Differential pressure balance is superior to other balance valve place is that it has no actuator, completely rely on the medium's own pressure difference to achieve the function of the balance system, saving energy and installation space, is an intelligent valve

 

Connection size 

 

 

TypeDNLDD1D2B-FZ-φDH
SK800X-16Q502031651259919-34-φ19155.5
6521618514511819-34-φ19178
8024120016013219-38-φ19185
10029222018015619-38-φ19197.5
12533025021018419-38-φ19240
15035628524021119-38-φ23246
20045834029526620-312-φ23324
25053040535531922-312-φ28350

 

Main technical performance

 

 

1.0MPA1.6MPA2.5MPANominal pressure
1.5MPA2.4MPA3.75MPAShell test pressure
1.1MPA1.76MPA2.75MPASeal test pressure
≤80℃Suitable temperature
waterApplicable medium

 

The working principle of

 

The 800X differential pressure bypass balance valve consists of the main and differential pressure control pilot valves, needle valves, ball valves and pressure gauges to form a hydraulic control pipe system. There are two water chambers inside the main valve, diaphragm water chamber for water passage, diaphragm water chamber for pressure control chamber. Its working principle is: when the pressure difference between the inlet and outlet of the main valve changes, the pressure difference between the pipe A and the pipe B changes, changing the opening of the pilot valve. When the pressure difference is large, the pilot valve opening is large, the water discharge in the control room through C pipe increases, the pressure in the control room of the main valve decreases, the main valve opening increases, and the pressure difference between the inlet and outlet of the main valve becomes small. On the contrary, if the pressure difference between the main valve inlet and outlet becomes smaller, the pilot valve opening becomes smaller, the pressure of the main valve control room rises, and the main valve opening becomes smaller and the pressure difference of the main valve increases. This negative feedback effect stabilizes the pressure difference between the main valve inlet and outlet at the set value. The pressure difference between the inlet and outlet of the main valve can be set by setting the needle valve opening and the pilot valve spring pressure

 

Hot Products

Y Model Or Thermal Power Type Steam Trap Flange End Or Threaded Y Strainer Valve Application The ...
Lever floating ball type cast steel Flanged connection Steam trap Y Strainer Valve Character Large ...
Ductile Iron Material Flange Connection Water Conservancy Valve Product introduction The valve body ...
PN1.6mpa Ductile Iron Reduced Pressure Regulator Valve Water Conservancy Valve The working principle ...
Ductile Iron Differential Pressure Bypass Valve Flange End Water Conservancy Valve Product ...
Pressure Relief Valve 1.6mpa Flange Water Conservancy Valve Product introduction The 500 pressure ...