Helpful tips on Generator Set Fault |
When fault occurs during generator set running,could do primary
judgement according to following tips. |
Icon | Indicator Light | Reason | Fault Analysis and Solve Method |
High Water Temperature Alarm | High Water Temperature Alarm | When water Temperature has risen to a level higher than or equal to
the sensor setting,the light is on. | Normally,it is caused by lack of Water or Oil Shortage,or Overload.
----Should Automatically Shutdown Generator set Immediately. |
Low Oil Pressure Alarm | Low Oil Pressure Alarm | When water Temperature has risen to a level higher than or equal to
the sensor setting,the light is on. | Normally,it is because of lack of Oil or Lubrication System Failure
which caused by refueling or replacing the Oil Filter.----- When
occurs this fault,should automatically shutdown generator set
immediately. |
Low Fuel Level Alarm | Low Fuel Level Alarm | When Fuel level has been detected by sensor fitted to the daily
tank,the light is off. | Normally,it caused by lacking of Water or Oil Shortage,or
Overload.-----When occures this Fault,should automatically shutdown
Generator set Immediately. |
Battery Charger Fault Alarm | Battery Charger Fault Alarm | The Charing System has fault while engine still running,the light
is off. | Battery Charging System Fault Caused.---The light in on at the
initial Start,when the charger reaches a certain speed,the light is
off.---This Failure will not lead to Automatic Shutdown Generating
Unit. |
Crank Failure Alarm | Crank Failure Alarm | When Generator set fail three times(or six times) in arow
starting,the light is on | It is caused by Oil Supply System or Re-Start System Failure. |
Overload or Breaker Tripping Alarm | Overload or Breaker Tripping Alarm | When Overloading or Short Circuit,the light is on. Tripping Circuit
Breaker cause generator set load out. | For this fault,it needs to load or unload some parts to eliminate
short-Circuit,and then re-close the circuit Breaker. |