Home Companies SUVEC E-Commerce Firm

American Standard UL Industrial Cables XHHW-2, 600V, type RW-90, power cable

SUVEC E-Commerce Firm
Active Member

Contact Us

[China] country

Address: No.58 Wenchang Road,Zhengzhou City,Henan Province,China

Contact name:Pinson

Inquir Now

SUVEC E-Commerce Firm

American Standard UL Industrial Cables XHHW-2, 600V, type RW-90, power cable

Country/Region china
City & Province zhengzhou henan
Categories Power Cables
InquireNow

Product Details

American Standard UL Industrial Cables
XHHW-2, 600V, type RW-90, power cable

Application and Description

 

  Type XHHW-2, type RW-90 building wire is intended for general
purpose applications utilized in conduit or other recognized
raceways for services, feeders, and branch-circuit wiring, as
specified in the National Electrical Code (NEC). Type XHHW-2 is
permitted to be used in wet or dry locations at temperatures not to
exceed 90ºC. Industrial environments where superior insulation
toughness and chemical resistance are required. Type XHHW-2 is
permitted for 600 volts applications. 1/0 AWG and larger may be
used in cable  tray in accordance with the National Electrical
Code. 1/0 AWG and larger comply with IEEE 1202/UL FT4 flame test
and ICEA T-29-520 (210,000 Btu/hr) flame test.  

Cable Construction

  

 


Conductor: Single copper conductor, stranded tinned annealed copper per ASTM B3 Class B stranding per ASTM B8
Insulation: Flame-retardant and moisture resistant Cross-Linked Polyethylene (FRXLPE)
Color: upon request, black is preferable
http://www.electriccablechina.com cable.pinson@gmail.com
Industrial Cables XHH / XHHW-2

Technical Characteristics


- UL 44 - Thermoset-Insulated Wires and Cables.
- UL 1685 - CT Flame Exposure Test.
- UL 1581- Flame Exposure Test (VW-1)
- IEEE 1202/FT4 (2/0 AWG and larger)
- Flame Test (70,000 Btu/hr Vertical Tray Test)).
- ICEA T-29-520 (210,000 Btu/hr) flame test
- ICEA S-95-658 (NEMA WC70)

Cable Parameter

  
AWG/
KCMIL
STRANDNOMINAL CONDUCTOR DIAMETER INCH/MMNOMINAL INSULATION THICKNESS INCH/MMNOMINAL OVERALL DIAMETER INCH/MMCOPPER 
WEIGHT 
LBS/KFT KG/KM
CABLE 
WEIGHT 
LBS/KFT KG/KM
1470.071.800.0300.760.133.3812181725
1270.092.260.0300.760.153.8420302639
1070.112.870.0300.760.184.5732483857
870.143.560.0451.140.246.1051766597
670.184.570.0451.140.287.118112199147
470.235.840.0451.140.338.38129192152226
270.297.370.0451.140.399.91205305233347
1190.328.130.0551.400.4411.18256381293437
1/0190.369.140.0551.400.4812.19326485364572
2/0190.4110.410.0551.400.5313.46411612453674
3/0190.4611.680.0551.400.5814.73518772565842
4/0190.5112.950.0551.400.6316.006539727061051
250370.5614.220.0651.650.7017.7872210748371246
350370.6616.760.0651.650.8020.321081160911571722
400370.7318.540.0651.650.8722.101235183813221967
500370.7920.070.0651.650.9323.621544229816342432
600610.8722.100.0802.031.0426.421853275819722935
750610.9824.890.0802.031.1529.212316344724483643

 

Hot Products

American Standard UL Industrial Cables XHH / XHHW-2 Application and Description The XHH conductor is ...
American Standard UL Industrial Cables XHHW-2, UL Type SIS1/XHHW-2, VW-1 Rated Application and ...
American Standard UL Industrial Cables XHHW-2, 600V, type RW-90, power cable Application and ...
American Standard UL Industrial Cables AL-XHHW-2 Power Cable, CT Rated Application and Description ...
American Standard UL Industrial Cables XHHW/PVC Jacket, Power Cable, CT Rated Application and ...
American Standard UL Industrial Cables XHHW/PVC,3-core,Type TC Power Cable Application and ...