High voltage electrical panel for substation model KYN28-12
Overview:
KYN28-12 indoor drawer style metal-clad electrical switchgear
1. General
KYN28-12 (Z) indoor drawer style metal-clad switchgear is a set of
power distribution device of rated voltage 3 to 12KV
three-phase AC 50Hz of single bus bar and single bus bar segmental
system. It is applicable to power transmission of the power plant,
power receiving and distribution of the electric system and the
substation of the industrial enterprises to fulfill the aims of
control, protection and inspection.
2. working condition
Environment temperature: -15°C to +40°C
Relative humidity: daily average ≤95% monthly average≤90%
Height above sea level: ≤1000m
Earthquake magnitude ≤8
No fire, explosion danger, serious pollution, or chemical erosion
occasion.
3.Main characteristics
The structure of the cabinet is bolt by aluminum zinc alloy board
after the process of CNC machine tool and multi bending technology;
All the operation can be done after the cabinet door is closed;
High protection degree, protect the intruder of sundries and pests;
Simple and effective “five-prevention” lock function, protect error
operation;
Can adopt VS1 and CD4 vacuum circuit breaker;Easy replacement of
the circuit breaker and free exchange of the drawers;
The cabinet can be installed by the wall, maintenance in the front,
which reduces the floor space;
Large space of the cable room can connect many cables;
The relay room and the cable room can respectively add a heater to
avoid freezing or erosion.
Technical Data
Item | Unit | Data |
Rated Voltage | kV | 3.6,7.2,12 |
Rated Frequency | Hz | 50 |
Rated Current of Circuit Breaker | A | 630,1250,1600,2000,2500,3150 |
Rated Voltage of Switchgear | A | 630,1250,1600,2000,2500,3150 |
Rated short-time withstand current (4s) | kA | 16,20,25,31.5,40,50 |
Rated Peak Withstand Current (Peak Value) | kA | 40,50,63,80,100,125 |
Rated Short-circuit Breaking Current | kA | 16,20,25,31.5,40,50 |
Rated Short- circuit Closing Current | kA | 40,50,63,80,100,125 |
1min Power Frequency Withstands Voltage | kV | 24, 32, 42 |
Lightning Withstands Voltage , Rated Insulation Leve | kV | 40, 60, 75 |
Protection Grade | Shell is IP4X, Shell is IP2X when compartment and circuit breaker doors are open |
Cabinet outline dimensions(mm)(not including door)
Height | Width | Depth |
2300 | 800 | 1800 |
2300 | 1000 | 1800 |
Working consitions
a. Ambient temperature: Maximum temperature:+40℃ Minimum
temperature: -15℃
b. Ambient humidity: Daily average RH no more than 95%;Monthly
average RH no more than 90%
c. Altitude no higher than 2500m;
d. The air around without any pollution of duty,smoke,ercode or
flammable air,steam or salty fog;