Guangdong Sunkings Electric Co., Ltd |
|
350Kva Continuous Duty Diesel Generator 1500RPM Shangchai Engine
General Information:
1. Prime Power 280Kw / 350Kva, standby power 308Kw / 385Kva.
2. 50Hz, 400 Volt / 230 Volt, 3 Phase 4 Pole, 0.8 power factor, 1500RPM.
Genset Specifications:
Genset model | SSF350 |
Genset rated power | 280KW / 350KVA |
Rated voltage | 400/230V (adjustable) |
Rated current | 504 Amps |
Frequency | 50 Hz |
Power factor | 0.8 Lagging |
Connecting type | 3 phase 4 wire |
Cooling system | Closed cycle water-cooled with fan, water tank |
Overall dimension (L×W×H) mm | 3100×1200×1800 |
Gross weight (kg) | 2500 |
Engine Specifications:
Diesel Engine | |
Brand | SHANGCHAI |
Model | SC13G420D2 |
Engine type | 6 cylinders in Line,4 stroke, direct injection |
Aspiration | Turbocharged and air-to-air intercooled |
Rotating speed | 1500 RPM |
Engine cooling system | Water-cooled |
Speed governing system | Electronic speed governor |
Starting method | By 24V batteries |
Engine filter system | Dry type air filter ,fuel filter, oil filter, water filter |
Displacement(L) | 12.88 |
Bore×Stroke(mm) | 135×150 |
Noise level (dB) | 115 |
100% Load fuel consumption (l/h) | ≤65.9 |
Lube capacity(L) | 33 |
Alternator Specifications:
Alternator | |
Brand | FARADAY |
Model | FD4LS1-4 |
Excite type | Brushless self-excited AVR regulation |
Connecting type | 3 phase 4 pole |
Steady frequency change | 0.50% |
No load voltage | ≥95%-105% |
Steady voltage | ≤±1% |
Insulation class | Class H |
Protection grade | IP23 |
Electrical Parameters
Wave distortion: <10%
Voltage fluctuation: <0.5%
Voltage / frequency fluctuation: <=0.5%
AVR self-regulated, voltage regulation rate: <=+- 1%
Radio interference restraining accords with stipulation of
VDE0875-N and ISO8528
Control Function
Key start / auto start
Monitoring meters: Current; Frequency; Wire Voltage; Genset KVA;
Genset KW; Output
Capacity; Output KW.H; Power Factor.
Warning/Shutdown: Alternator Under/Over Volts, Frequency;
Under/Over Speed; Low Oil Pressure; High Engine Temp; High/Low
Battery Volts; Over Current; Earth Fault Shutdown.