Home Companies Ningbo Suntech Power Machinery Tools Co.,Ltd.

10KV And 35KV Cable Testing Machine, High Voltage Ac Testing Equipment

Ningbo Suntech Power Machinery Tools Co.,Ltd.

Contact Us

[China] country

Trade Verify

Address: NO.61 Xiachen'an Road,Xiwu Street,Fenghua District,Ningbo,China.315505

Contact name:Peter

Inquir Now

Ningbo Suntech Power Machinery Tools Co.,Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

10KV And 35KV Cable Testing Machine, High Voltage Ac Testing Equipment

Country/Region china
City & Province ningbo zhejiang
Categories Tool Parts
InquireNow

Product Details

Portable Variable Frequency Resonant Withstand Voltage Test Set , For 10KV and 35KV Cable Test

 

I. Product Usage :


This test set model CHX-405KVA/27KV, 54KV is designed for 10KV and 35KV class XLPE cable on-site AC withstand voltage test with variable frequency resonant circuit technology; the highest test voltage is no more than 22KV or 52KV; test frequency: 30-300Hz; the duty cycle is no more than 60mints. it can help customers to perform preventive test or hand-over test on AC withstand voltage test for XLPE cables 35KV within 3km and 10KV class within 7km .

Test range of the set is as following:

1. 3km of 35kV/300mm2 cable, tested capacitance ≤0.5835uF, test frequency 30-300Hz, test voltage 52kV, test time 60min.

2, 7km of 10kV/300mm2 cable , tested capacitance ≤ 2.62uF, test frequency 30-300Hz, test voltage 22kV, test time 5min.

 

 

II. General Technical Data

 

  1. Rated capacity: 405kVA;
  2. Input power: three-phase 380V voltage, frequency is 50Hz;
  3. Rated voltage: 27kV; 54kV;
  4. Rated current: 15A; 7.5A;
  5. Working frequency: 30-300Hz;
  6. Device output waveform: sine wave
  7. Waveform distortion rate: output voltage waveform distortion rate ≤ 1%;
  8. Working time: continuous 60min allowed under rated load; overpressure 1.1 times 1 minute;
  9. Temperature rise: temperature rise ≤65K after continuous operation for 60 minutes under rated load;
  10. Quality factor: device itself Q≥30 (f=45Hz);
  11. Protection function: Over-current, over-voltage and test product flashover protection for the tested product (see the variable frequency power supply section for details);
  12. Measurement accuracy: system effective value 1.5;


III. Main Components:

 

SNName of ComponentsType and specificationQty.Each weightEach Dimension
1Variable frequency powerFKVF-30kW/380V1piece35kgs480*480*520mm
2Excitation transformerCQSB(J)-25kVA/1.5KV,3KV1piece80kgs550*550*580mm
3HV resonant test reactorCHX(kf)-67.5kVA/27kV/50H10pieces65kgsD480*H520mm
4Capacitive dividerTRF-60kV/3000pF1set10kgsD150*H650mm
5Special test accessories 1set  

 

 
 
 
 
 
 
 
 
 
 

IV. Test priciple :
10KV And 35KV Cable Testing Machine , High Voltage Ac Testing Equipment 0

VF: Variable Frequency Power Source T : Excitation Transformer
L : Test Reactor Cx: Tested Equipment MOA1: Lightning Arrestor
C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm )


V. Main Measuring and control software panel:
10KV And 35KV Cable Testing Machine , High Voltage Ac Testing Equipment 1
Note: This is the software panel before start test for parameter setting

 


VI.Accessories

  • Accessory box for storage accessoires
  • Input cables of power source
  • Output cables of power source
  • Output cables of exciting transformer
  • System grounding cables
  • Parallel cables of the reactor
  • HV measuring cables ( the signal output cables of voltage divider )
  • HV output cables(reactor to divide,divider to test object)
  • A final test report, a quality Certificate ,a user manual and a packing list are offered .


VII. Other Optional Model

 

1. For GIS on-site test

ModelRated voltageRated output currentRated output capacity

Application

(From 45Hz starting)

CHX-135KVA/135KV27KV*51A135KVAFor 72.5KV and below GIS
CHX-270KVA/135KV27KV*51A135KVAFor 72.5KV and below GIS
CHX-216KVA/216KV27KV*81A216KVAFor 123KV and below GIS
CHX-270KVA/270KV27KV*101A270KVAFor 145KV and below GIS
CHX-275KVA/275KV275KV2A275KVAFor 170KV and below GIS
Special requirement can be made by order

 

 

2. For 45KV XLPE cable on-site test

ModelRated voltageRated output currentRated output capacityMax Application
CHX-108/5454KV2A108KVA45kV cable≤1km
CHX-216/5454KV4A216KVA45kV cable≤2km
CHX-324/5454KV6A324KVA45kV cable≤3km
CHX-432/5454KV8A432KVA45kV cable≤4km
CHX-540/5454KV10A540KVA45kV cable≤5km
CHX-1080/5454KV20A1080KVA45kV cable≤10km
Special requirement can be made by order

 

3. For 66KV XLPE cable on-site test

ModelRated voltageRated output currentRated output capacityMax Application
CHX-160/8080KV2A160KVA66kV cable≤0.5km
CHX-320/8080KV4A320KVA66kV cable≤1km
CHX-640/8080KV8A640KVA66kV cable≤2km
CHX-960/8080KV12A960KVA66kV cable≤3km
CHX-1280/8080KV16A1280KVA66kV cable≤4km
CHX-1600/8080KV20A1600KVA66kV cable≤5km
CHX-3200/8080KV40A3200KVA66kV cable≤10km
CHX-9600/8080KV120A9600KVA66kV cable≤20km
Special requirement can be made by order

 

 

 

VIII. On-site insulation test standard table from IEC 60840:2011 for XLPE cable

10KV And 35KV Cable Testing Machine , High Voltage Ac Testing Equipment 2

Hot Products

SKDP Model 10KN Parallel Earth Wire Gripper Come Along Clamp Basic Construction Tools Suntech Power ...
PD Free AC Resonant Test Systems , No Corona Induced Withstand Voltage Test Sets I. Product ...
Variable Frequency AC Resonant Withstand Voltage Test Set , Variable Frequency Resonant Control Unit ...
Portable Variable Frequency Resonant Withstand Voltage Test Set , For 132KV GIS Test I. Application ...
Portable Variable Frequency Resonant Withstand Voltage Test Set , For 110KV Powe Substation Test Set ...
Portable Variable Frequency Resonant Withstand Voltage Test Set , For 10KV and 35KV Cable Test I. ...