XR60CX Dixell Digital Refrigeration Controllers,Digital Temperature Controller For Coldroom And Freezer

GENERAL DESCRIPTION
 
Model XR60CX, format 32 x 74 mm, is microprocessor based controller, suitable for applications on
medium or low temperature ventilated refrigerating units. It has three relay outputs to control
compressor, fan, and defrost, which can be either electrical or reverse cycle (hot gas). It is also
provided with three NTC or PTC probe inputs, the first one for temperature control, the second one,
to be located onto the evaporator, to control the defrost termination temperature and to managed the
fan, the third one, optional, to connect to the HOT KEY terminals to signal the condenser
temperature alarm or to display a temperature. The digital input can operate as fourth temperature
probe.
 
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a
network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It
allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.
 
SPECIFICATIONS / MODELS 
 
 XR01CXXR02CXXR03CXXR04CXXR06CX
Dimension     
32*74*50mm 
32*74*60mm    
Power supply     
12,24V ac/dc (± 10%)
115,230V ac/dc (± 10%)
Temperature sensor     
Coldroom Temp Probe NTC / PTC√ / optional√ / optional√ / optional√ / optional√ / optional
Defrost / Fan Probe NTC / PTC√ / optional√ / optional√ / optional√ / optional√ / optional
Function digital signal input 
Outout     
Load or compressor20A / 8A20A / 8A20A / 8A20A / 8A20A / 8A
Defrost Shut down defrostShut down defrost8A8A
Fan    8A
Light / Auxiliary output  8A  
Others     
Hot Key Programming key
Heating / CoolingHeating / CoolingHeating / CoolingHeating / CoolingCoolingCooling

 

 

 XR10CXXR20CXXR30CXXR40CXXR50CXXR60CXXR70CX
Dimension       
32*74*60mm
Power supply       
12,24V ac/dc (± 10%) 
115,230V ac/dc (± 10%)
Display       
3 digital tubes, minus sign,Decimal point,Output status minus sign
Temperature sensor       
Coldroom Temp Probe NTC / PTC
Evaporator Probe NTC / PTC
second Evaporator Probe NTC / PTC   
Condenser Probe NTC / PTC
Digital input/display probe       
Alarm,Trigger Defrost,Auxiliary probe, door switch,Pressure switchSettableSettableSettableSettableSettableSettableSettable
Relay Outout       
compressor20A / 8A20A / 8A20A / 8A20A / 8A20A / 8A20A / 8A/16A20A / 8A/16A
Defrost   8A8A8A8A/16A
Evaporator Fan     5A/8A5A/16A
Light / Alarm output  8A 5A/8A 8A/16A
Others       
Hot Key Programming key
Serial Interface MODBUS
 
DEFROST
 
Two defrost modes are available through the “td” parameter:
 
• td=EL → defrost through electrical heater (compressor OFF)
• td=in → hot gas defrost (compressor ON).
 
Other parameters are used to control the interval between defrost cycles (id) ), its maximum length (Md) and two defrost modes: timed or controlled by the evaporator’s probe. At the end of defrost dripping time is started, its length is set in the dt parameter. With dt=0 the dripping time is disabled
 
FANS
With FC parameter it can be selected the fans functioning:
 
• FC=cn → will switch ON and OFF with the compressor and not run during defrost
• FC=on → fans will run even if the compressor is off, and not run during defrost
 
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fd” parameter.
 
• FC=cy → fans will switch ON and OFF with the compressor and run during defrost
• FC=oY → fans will run continuously also during defrost.
 
An additional parameter “FS” provides the setting of temperature, detected by the evaporator probe, above which the fans are always OFF. This is used to make sure circulation of air only if his temperature is lower than set in “FS”
 
FANS AND DIGITAL INPUT
 
When the digital input is configured as door switch iF=do, fans and compressor status depends on the dC parameter value:
• dC=no → normal regulation;
• dC=Fn → fans OFF;
• dC=cP → compressor OFF;
• dC=Fc → compressor and fans OFF.
When rd=y, the regulation restart with door open alarm.
 
FRONT PANEL COMMANDS
 

 

HOW TO SEE THE SET POINT
 
1.Push and immediately release the SET key, the set point will be showed;
2.Push and immediately release the SET key or wait about 5s to return to normal visualisation.
 
HOW TO CHANGE THE SETPOINT
1.Push the SET key for more than 2 seconds to change the Set point value;
2.The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3.To change the Set value push the or arrows.
4.To memorise the new set point value push the SET key again or wait 10s.
 
HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 seconds and a manual defrost will start
 
HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the SET+keys for 3s (“°C” or “°F” LED starts blinking).
2. Select the required parameter. Press the “SET” key to display its value
3. Use ↑ or ↓  to change its value.
4. Press “SET” to store the new value and move to the following parameter.
 
To exit: Press SET+↑ or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
 
ALARM SIGNALLING
 
Mess.          Cause                                             Outputs
"P1"              Room probe failure                          Compressor output according to “Cy” e “Cn”
"P2"              Evaporator probe failure                  Defrost end is timed
"HA"              Maximum temperature alarm            Outputs unchanged
"LA"              Minimum temperature alarm             Outputs unchanged
“EA”              External alarm                                  Outputs unchanged
“CA”              Serious external alarm                     All outputs OFF
“dA”               Door Open                                      Compressor and fans restarts
 
 
 
 
 
 

 

Hot Products

XR75CX-5N7C3 Dixell Digital Controller For Medium-Low Temperature Refrigeration Applications With ...
XR70CX-5N0C3 Dixell Digital Controller With Defrost And Fan Management With Probe NTC PTC GENERAL ...
DIXELL DIGITAL CONTROLLER WITH DEFROST AND FANS MANAGEMENT XR06CX-5N0C1 WITH PROBE NTC GENERAL ...
Italy Dixell Digital Temperature Controllers XR02CX-5N0C1 With Sensor For Coldroom And Freezer ...
XR60CX Dixell Digital Refrigeration Controllers,Digital Temperature Controller For Coldroom And ...
ID Plus 971 / 974 Eliwell Electronic Controllers For Refrigeration Unit,Eliwell Digital Controller ...