Product Details

I.Application:

  • GDJB is applied to test the relay unit in relay protection system. 
  • At the same time it could be considered as a universal three phase AC/DC voltage source or current source.

II.Functions:

  • AC current and voltage based protection relay unit test
  • DC current and voltage based protection relay unit test
  • Frequency protection relay unit test
  • Harmonic protection relay unit test
  • Differential protection relay unit test
  • Zero-sequence protection relay unit test
  • Distance protection relay unit test
  • Power system network fault simulation

III.Technique Index:

  • Max AC current output 30A at per phase limited in 10s, 90A at three phases in parallel limited in 10s, Frequency 20~1000Hz, Continuous current output 10A at per phase , Capacity 420VA at per phase
  • Max DC continuous current output ±10 at per phase, maximum voltage 20V, 30A output at three phase in paralle
  • Max AC voltage output 120V at per phase, 240V at phase to phase, Frequency 20~1000Hz, capacity 80VA at per phase, 100VA at phase to phase
  • Max DC voltage output ±160V at per phase, ±320V at phase to phase, capacity 70VA
  • Time counter 0.1ms~9999s, error < 0.1ms
  • AC current and voltage error <0.5%RDG+0.05%FS
  • DC current error<0.5%RDG+0.05%FS, DC voltage error 1%RDG+0.1%FS
  • Binary input: Active node 0~250V, 0~6V for “0”, 6~250V for “1”, passive node: 20mA max
  • Binary output: DC 220V/0.2A, AC 220V/0.5A
  • Power supply:AC220V ± 10%, 50Hz/60Hz
  • Environment temperature: 0~50°C
  • Humidity: ≤85%RH
  • Weight:<18KG

Hot Products

I. Function Breakdown test of user-defined Proof test IEC60156/IS6792/BS5874 test ASTM D1816 ...
I. Function Breakdown test of user-defined Proof test Calibration interface for customers Uploading ...
I. Function Breakdown test of user-defined Proof test Calibration interface for customers Uploading ...
Test Sample :Single-Phase and Three-Phase Transformer , CT ,PT I.Functions 1. The voltage ratio ...
I.Application: GDJB is applied to test the relay unit in relay protection system. At the same time ...
I.Features Measure transformer No-load current, No-load loss, short circuit voltage, short circuit ...