No.Functions
1Closing and opening time measurement of 12 channels
2Max difference of closing or opening time measurement of three phases
3Bounce time and frequency measurement of breaker closing
4Circuit breaker closing and opening speed measurement
5Travel-time, Coil current-time curve of circuit breaker operation measurement
6Clearance of circuit breaker measurement
7Variable DC circuit breaker operation power supply
8Print test results by internal micro printers
Technical Data

1) Time measurement range: 6000ms, resolution 0.1ms

Time measurement error <1%RDG+0.2ms
2) Speed measurement:
Range 2m/s resolution 0.01m/s max error<0.1m/s
Range 20m/s resolution 0.01m/s max error<0.2m/s

3) Travel measurement:

Range 250.0mm resolution 1mm max error 1mm

4) DC Power out: DC30V~250V/10A (instantaneous)

5)9 Travel sensors configuration: grating and angle

6) Test standard: IEC62271

7) LCD: 128*64

8) Power supply: AC220V±10% 50Hz/60Hz

9) Temperature: 0~50°C humidity: <90%

10) Size: 400mm*250mm*200mm

11) Weight: 7kg

 

Hot Products

I---Technical Data: 12 Standard Phase Voltages/Currents: Providing standard 12 phase voltages...
SPECIFICATIONS Basic Functions Range Best Accuracy DC Voltage 60mV/600mV/6V/60V/600V/1000V (0.5%+1) ...
I.Application GDDZ insulating gloves and boots is application to test leakage current,insulation ...
Model Measurement range General introduction GD2550 2500V/0~100GΩ; 5000V/0~200GΩ; Analog , Short ...
No. Functions 1 Closing and opening time measurement of 12 channels 2 Max difference of closing or ...
I.Application Tests for current transformer: 1)Excitation curve and parameters test 2)Turns ratio ...