Wuhan Unique Mechanical And Electrical Equipment Co.,LTD. |
|
BS 5266-1 Standard Fire Resistance Cable for Normal Emergency Lighting
APPLICATION
A fire resistant, flexible LSZH (Low Smoke Zero Halogen) cable suitable for normal emergency lighting, fire alarms and voice alarm systems.
CABLE STANDARDS
BS 5266-1, 8.2.2(b) and (d) Emergency lighting, BS 8434-2,
BS 5839-8, BS 5839-1, 26.2e
BS EN 50200 - PH30, PH60, PH120 BS 6387 C W and Z
LUL 1-085, IEC 331-3, 120 mins in conduit
DIMENSIONS
UNI-Cables PART NO. | NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km |
UNIFR03015 | 3 | 1.5 | 10 | 135 |
UNIFR03025 | 3 | 2.5 | 11.2 | 168 |
UNIFR04015 | 4 | 1.5 | 11.2 | 149 |
UNIFR04025 | 4 | 2.5 | 12.4 | 211 |
CONDUCTOR
NOMINAL CROSS SECTIONAL AREA mm² | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km |
1.5 | 13.3 |
2.5 | 7.98 |
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NOMINAL CROSS SECTIONAL AREA mm² | CURRENT RATING (CLIPPED DIRECT) | |
Single Phase AC or DC Amps | Three Phase AC Amps | |
1.5 | 23 | 21 |
2.5 | 31 | 28.5 |
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² | DC mV/A/M | SINGLE PHASE AC mV/A/m | THREE PHASE AC mV/A/m |
1.5 | 34.1 | 34 | 29.7 |
2.5 | 20.9 | 21 | 17.6 |