Description of DORIN INVERTER CO2(R744) Heat Pump Systems – for both Practical and Cost-Saving Benefits

The compressor sucks low-temperature and low-pressure gaseous carbon dioxide refrigerant from the evaporator, and compresses the carbon dioxide refrigerant into a high-temperature and high-pressure supercritical fluid through work. The high-temperature and high-pressure supercritical fluid enters the gas cooler to exchange heat with water, and is cooled in the gas cooler. The high-pressure fluid releases a lot of heat, and the water absorbs the heat released and the temperature continues to rise. After the high-pressure fluid is throttled and depressurized by the expansion valve, it absorbs heat from the surrounding air and evaporates into low-pressure gas through the action of the fan in the evaporator, and is sucked into the compressor to be compressed, and the cycle is repeated to produce hot water. Features Natural environmental protection refrigerant: ODP is 0, GWP is 1, no pollution to the environment, non-toxic, non-flammable Excellent high-temperature heating performance: the highest water output can reach above 90℃ Excellent low temperature performance: at -20°C ambient temperature, 90°C high temperature hot water can still be produced High efficiency: the heating performance COP can reach 4.5, and when the hot water is produced at low temperature, the COP is still above 2.0 Wide range of application: it can work normally in the ambient temperature range of -20℃~43℃, suitable for our production of domestic or industrial hot water

 

Performance of DORIN INVERTER CO2(R744) Heat Pump Systems – for both Practical and Cost-Saving Benefits

Ultra-low temperature working conditions: ambient temperature DB-10-C, water inlet temperature 9°C;
Defrost condition: ambient temperature DB2°C/WB1°C, water inlet temperature 9°C; low temperature condition: ambient temperature DB7°C/WB6°C, water inlet temperature 9°C; standard working condition: ambient temperature DB20°C /WB15°C, inlet water temperature 15°C; high temperature working condition: ambient temperature DB38°C/WB23°C, inlet water temperature 29°C.
Installation Notes:
1. The spacing around the installation must not be less than Im;
2. The pipelines other than the heat pump should be protected from frost and heating elements can be installed;
3. Heat insulation and protection measures should be taken for the pipelines for hot water circulation to prevent heat loss.

HPA/mmB/mmC/mm
7.514509501450
1016009501500
15185011501900
20205011501950
30267014102150
40229022701980

 

Application Diagram Pressure-bearing water tank 

DORIN INVERTER CO2(R744) Heat Pump Systems – for both Practical and Cost-Saving Benefits

System Diagram Smart Control System

DORIN INVERTER CO2(R744) Heat Pump Systems – for both Practical and Cost-Saving Benefits

 

CO2 heat pump hot water unit specification list  

R744 CO2 Air Source Heat Pump Water Heater for Residential Heating 7.45kw output of 90 degree with dorin compressor

ModelSJKRS-05I/CSJKRS-28II/CSJKRS-36II/CSJKRS-55II/CSJKRS-73II/CSJKRS-106II/CSJKRS-160II/C
Specification2HP7.5HP10HP15HP20HP30HP45HP
Power supply230V/1N/50Hz380V/3N/50Hz
Heating MethodDirect heating / circulating
Nominal working condition( kw)heating capacity7.4528.137.756.174.1108.6158.7
( kw)
Input power
1.616.18.212.216.123.634.5
COP4.64.64.64.64.64.64.6
( m³/h)
Heating water flow
0.110.60.811.211.622.333.41
High temperature working conditions(kw)heating capacity5.5823.928.551.559.589131.5
( kw)Input power1.737.58.916.118.627.841.1
COP3.23.23.23.23.23.23.2
( m³/h)
Heating water flow
0.070.270.330.590.681.021.51
Low temperature working conditions(kw)heating capacity4.315.719.131.838.959.390
( kw)Input power1.595.87.111.814.421.933.3
COP2.72.72.72.72.72.72.7
(m³/h)
Heating water flow
0.070.280.340.560.681.041.52
Parts informationWater pipe interface sizeDN15DN20DN25DN32
Water heat exchangerPlate or tube heat exchanger
Air heat exchangerCopper tube aluminum fins
Compressor typeDouble rotarySemi-closed reciprocating type
Operation panelColor touch screen
Maximum outlet temperature85℃90℃
RefrigerantR744(CO2)
Design pressur(MPa)15MPa(HP)/8MPa(LP)
Dimensions (L,W,H mm)750*390*12451450*950*14501600*950*15001850*1150*19002050*1150*19502670*1410*21502070x2150x2245
( dB) Noise≤44≤56≤59≤62≤67≤70≤70
( kg) Weight8355066078086011801360
Feedwatertemperature(℃)5~40
( Feed water pressure MPa)0.05~0.4
Water Outlet temperature (℃)55~8555~90
Maximum flow0.241.21.52.43.24.96.5
Ambient temperature (℃)-25~43

 

System schematic diagram

 


Hot Products

Strength of Commercial REVERE CO₂ R744 Air to Water Heat Pump 40kw A carbon dioxide heat pump device ...
R744 CO2 Air Source Heat Pump Water Heater For Residential Heating 7.45kw Output Of 90 Degree With ...
R744 CO2 Air To Water Heat Pump 160kW Commercial Usage For Heating And Cooling Hot Water -30degree ...
Description of AC Inverter CO2 Heat Pump Residential CO2 heat pump system for combined space heating ...
Description of DORIN INVERTER CO2(R744) Heat Pump Systems – for both Practical and Cost-Saving ...
DORIN INVERTER CO2(R744) Heat Pump Systems Carbon Dioxide High Temperature Heat Pump Air Source And ...