AKH-0.66/K Series Split Core Current Transformer
AKH -0.66K series open-type current transformers are mainly used in
industrial urban and rural power grid reconstruction projects.
They are easy to install and do not need to disassemble the primary
busbar. They can also be used for live measurement and metering
devices. operation, without affecting the normal electricity
consumption of customers, saving manpower, material and financial
resources for user transformation projects, and improving
efficiency. This series of current transformers can be used in
conjunction with relay protection measurement and metering devices.
Size and dimensions
Size(mm) Specification | Outline size | Through size | Mountng size | Tolerance | |||||
W | H | D | a | e | P | Q | |||
K-30×20 | 90 | 114 | 40 | 22 | 32 | 50 | 32 | ±1 | |
K-60×40 | 114 | 140 | 36 | 42 | 62 | 45 | 33 | ||
K-80×40 | 122 | 162 | 40 | 42 | 82 | 45 | 33 | ||
K-80×50 | 114 | 159 | 36 | 52 | 82 | 45 | 32 | ||
K-80×80 | 144 | 159 | 36 | 82 | 82 | 45 | 33 | ||
K-120×80 | 144 | 194 | 52 | 42 | 102 | 56 | 36 | ||
K-120×60 | 164 | 214 | 52 | 62 | 122 | 56 | 36 | ||
K-100×40 | 144 | 199 | 36 | 82 | 122 | 45 | 32 | ||
K-130×40 | 144 | 224 | 52 | 42 | 132 | 56 | 36 | ||
K-130×50 | 145 | 222 | 50.5 | 54 | 130 | 56 | 36 | ||
K-130×60 | 170 | 222 | 70 | 60 | 130 | 56 | 36 | ||
K-140×60 | 164 | 234 | 52 | 62 | 142 | 56 | 36 | ||
K-160×80 | 184 | 254 | 52 | 82 | 162 | 56 | 36 | ||
K-200×80 | 184 | 294 | 52 | 82 | 202 | 56 | 36 |
4.Cross-reference tables of spec.-parameter | ||||||||||
Type | Rated current ratio(A) | Precision degrec | Rated load,VA | |||||||
K-30×20 | 20-75/1A | 0.2 | ||||||||
100-150/5(1)A | 1 | |||||||||
200/5(1)A | 1 | 1.5 | ||||||||
250-300/5(1)A | 0.5 | 1.5 | ||||||||
350-400/5(1)A | 0.5 | 2.5 | ||||||||
K-60×40 | 250-300/5(1)A | 1 | 1.5 | |||||||
350-450/5(1)A | 0.5 | 1.5 | ||||||||
500-800/5(1)A | 0.5 | 2.5 | ||||||||
1000-1250/5(1)A | 0.5 | 5 | ||||||||
1500-2000/5(1)A | 0.5 | 10 | ||||||||
K-80×40 | 350-450/5(1)A | 0.5 | 2.5 |
| 500-800/5(1)A | 0.5 | 5.0 | |
1000-2000/5(1)A | 0.5 | 10 | ||
2500/5(1)A | 0.2 | 10 | ||
K-80×50 | 250-300/5(1)A | 1 | 1.5 | |
400-450/5(1)A | 0.5 | 1.5 | ||
500-800/5(1)A | 0.5 | 2.5 | ||
1000/5(1)A | 0.5 | 5 | ||
K-80×80 | 250-300/5(1)A | 1.5 | ||
400-450/5(1)A | 0.5 | 1.5 | ||
500-800/5(1)A | 0.5 | 2.5 | ||
1000/5(1)A | 0.5 | 5 | ||
K-100×40 | 1000-2000/5(1)A | 0.5 | 10 | |
2500-3000/5(1)A | 0.2 | 10 | ||
4000A/5(1)A | 0.2 | 15 | ||
K-120×60 | 400-450/5(1)A | 0.5 | 2.5 | |
500-800/5(1)A | 0.5 | 5.0 | ||
1000-2000/5(1)A | 0.5 | 10 | ||
2500-4000/5(1)A | 0.2 | 10 | ||
K-120×80 | 500-800/5(1)A | 0.5 | 2.5 | |
1000-1200/5(1)A | 0.5 | 5 | ||
1250-1500/5(1)A | 0.5 | 7.5 | ||
K-130×40 | 1000-2000/5(1)A | 0.5 | 10 | |
2500-4000/5(1)A | 0.2 | 10 | ||
K-130×50 | 1000-2000/5(1)A | 0.5 | 10 | |
2500-3000/5(1)A | 0.2 | 10 | ||
4000-5000/5(1)A | 0.2 | 15 | ||
K-130×60 | 1000-2000/5(1)A | 0.5 | 10 | |
2500-5000/5(1)A | 0.2 | 15 | ||
K-140×60 | 1000-2000/5(1)A | 0.5 | 10 | |
2500-3000/5(1)A | 0.2 | 10 | ||
4000-5000/5(1)A | 0.2 | 15 | ||
K-160×80 | 1000-2000/5(1)A | 0.5 | 10 | |
2500-3000/5(1)A | 0.2 | 10 | ||
4000-5000/5(1)A | 0.2 | 15 | ||
K-200×80 | 1000-2000/5(1)A | 0.5 | 10 | |
2500-3000/5(1)A | 0.2 | 10 | ||
4000-5000/5(1)A | 0.2 | 15 |