Home Companies Achievers Automation Limited

RD0-FB-Ex4.* PEPPERL FUCHS Isolated Barrier With 4 Outputs

Achievers Automation Limited

Contact Us

[China] country

Trade Verify

Address: RM 509, 5/F, THE CLOUD, 111,TUNG CHAU STREET, TAI KOKTSUI, KOWLOON,HONG KONG

Contact name:Caroline Chan

Inquir Now

Achievers Automation Limited

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

RD0-FB-Ex4.* PEPPERL FUCHS Isolated Barrier With 4 Outputs

Country/Region china
City & Province hong kong
Categories Solar Chargers
InquireNow

Product Details

Product Details:
Manufacturer : Pepperl+Fuchs
Product No. : RD0-FB-Ex4.*
Product Type : FieldBarrier
 
Features:

  • 4 outputs Ex ia IIC
  • FieldBarrier in Zone 1/Div. 2
  • Instruments in Zone 0...1/Div. 1
  • Short circuit current limitation per output
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Power, Com, and Error LEDs
  • Supports FISCO and Entity
  • Integrated cable tie-downs
  • Supports all grounding methods

Function
The FieldBarrier, a device coupler for DIN rail mounting, connects 4 instruments with intrinsic safety (Ex ia/Ex ib) and short circuit current limitation at each output. This ensures proper operation of the segment during faults or hot work at the spur.

High power on the trunk enables maximum cable lengths and device count in any hazardous area. The integrated fieldbus terminator features high-availability design and is selectable.

Output terminals with a choice of fixed or plug-in screw terminals connect 1 device each. LEDs simplify troubleshooting and help decrease repair time. Any grounding and shielding concept is possible based on FieldConnex ® enclosure solutions.

 

 

Technical data

 

1. General specifications
    Design / Mounting: Cabinet installation
2. Fieldbus connection
    Main cable (Trunk)
        Connection: input (Trunk IN): terminals 3+, 4-, 5s
        output (Trunk OUT): terminals 7-, 8+, 6s
        Rated voltage: 32 ... 16 V DC
        Rated current: 31 mA ... 26 mA (without load)
                                77 mA ... 115 mA (at 20 mA load per input)
                                120 mA ... 209 mA (at 40 mA load per input)
                                135 mA ... 241 mA (short-circuit on all outputs)
        Voltage drop: trunk IN to trunk OUT 100 mV max.
        Number of couplers: max. 4 per segment
    Outputs
        Number of devices per output: 1
        Connection: output 1: terminals 10+, 11-, 12S shield;
                            output 2: terminals 13+, 14-, 15S shield;
                            output 3: terminals 16+, 17-, 18S shield;
                            output 4: terminals 19+, 20-, 21S shield
        Rated voltage: 10 ... 13 V
        Rated current: max. 43 mA
        Short-circuit current: 50 mA
3. Indicators/operating means
    LED voltage Fieldbus: green: on, bus voltage existent
    LED status output: red flashing: short-circuit
4.Galvanic isolation
    Main wire/outputs: isolation is not affected by interference according to EN 50020, voltage peak value 375 V
5. Directive conformity
    Electromagnetic compatibility
        Directive 2014/30/EU: EN 61326-1:2013
6. Standard conformity
    Electromagnetic compatibility: NE 21:2006
    Degree of protection: IEC/EN 60529
    Fieldbus standard: IEC 61158-2
    Climatic conditions: DIN IEC 721
    Corrosion resistance: acc. to ISA-S71.04-1985, severity level G3
7. Ambient conditions
    Ambient temperature: -50 ... 70 °C (-58 ... 158 °F)
    Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
8. Mechanical specifications
    Connection type fixed: terminals, plug-in terminals
    Core cross section: up to 2.5 mm2
    Housing: see figure 1
    Housing material: Polycarbonate
        R... DIN rail housing: PA 6.6
    Degree of protection: IP20
    Mass: 1050 g
    Mounting: mounting on DIN rail in cabinet
9. Data for application in connection with hazardous areas
    EU-type examination certificate: PTB 02 ATEX 2086
    Main cable (Trunk)
        Maximum safe voltage Um :253 V AC
    Outputs
        Power: 975 mW
        Voltage: 15.75 V
        Current: 248 mA
 

 

Related Models:

KCD2-SCD-EX1NBB5-18GM50-E2-V1
KCD2-STC-EX1.20NBB8-18GM60-A2-V1
KFA6-DWB-EX1.DNBN3-F25F-E8-V1
KFA6-SR2-Ex2.WNBN40-U1K-N0
KFD0-CS-Ex1.50PNBN40-U4LK-N0
KFD0-HMS-16NBVB15-U1.Z2
KFD0-RSH-1.4S.PS2NCB5-18GM40-NO
KFD0-SD2-EX1.10100NJ10-30GM-N-5M
KFD0-SD2-EX1.1045NJ15-30GK-N
KFD2-UT2-1NJ2-12GK-SN
KFD2-CD-1.32NJ2-12GM-N
KFD2-CD-EX1.32NJ4-12GK-SN
KFD2-HMM-16NJ5-18GK-N
KFD2-SH-EX1.TNJ5-18GK-N-150
KFD2-SH-Ex1.T.OPNJ5-18GM-N
KFD2-SL2-EX2.BNJ8-18GK-N
KFD2-SR2-EX1.WRD0-FB-EX4
KFD2-SR2-Ex2.WRD0-FB-EX4.COM
KFD2-STC5-1.2OSC3,5-G-N0
KFD2-STC5-Ex1SC3,5-G-N0-5M
KFD2-STC5-Ex1.HSC3,5-G-N0-6M
KFD2-UT2-1SJ3,5-N
KFD2-VR4-EX1.26SJ3,5-S1N
KFU8-UFC-1.DUPR-03
KFU8-UFTV15-G-2M
K-HM26-2M-261533Z 787
NBB15-U1-E2Z787.H
NBB15-U1-Z2HIC2031

 
Company Introduction:
Achievers Automation Limited has more than 10 years experience in the market of Industrial Automation, specialized in reselling factory sealed Probe, Sensor, DCS,isolator barrier, HMI, PLC,Adapter,Profibus connector and cable from Brands as BENTLY NEVADA, Endress+Hauser, YOKOGAWA,MTL,Allen-Bradley, Pepperl+Fuchs,Rosemount, ASCO, Schneider, Lenze, Pro-face, Mitsubishi, Omron, Lenze, Delta, Honeywell, Siemens and etc. If you have any request, please do not hesitate to contact us.
 
FAQ of Achievers
Q:Are the Products Genuine OEM Units?
A: These items have been certified by Achievers Automation Limited to be genuine OEM Units obtained through OEM or independent third-party channels.
Q:How will you arrange shipment?
A: We can arrange shipment based on your request. We have cooperated forwader who can arrange shipment via FedEx, DHL,TNT with good price.
Q:What is the warranty of goods?
A: One-year Warranty.

 

Hot Products

Product Details: Manufacturer : Pepperl+Fuchs Product No. : KFD0-HMS-16 Product Type : HART ...
Product Details: Manufacturer : Pepperl+Fuchs Product No. : RD0-FB-Ex4.* Product Type : FieldBarrier ...
Pepperl+FuchsZener Barrier Z787 product details Manufacturer : Pepperl+Fuchs Type : DC version, ...
Datasheet excerpt: Technical data of NJ5-18GK-N General specifications Switching function Normally ...
PEPPERL FUCHS KFD2-UT2-1 Universal Temperature Converter Configurable By PACTware Product Details: ...
Pepperl+Fuchs Process Automation KCD2-SCD-EX1 Compact Analog Output W/Hart Product Details: ...