TEST-330B Three Phase microcomputer relay protection tester For distance fault protection

 

 

GFUVE ELECTRONICS is one of the leading relay protection tester manufacturers China, welcome to import cheap and discount relay protection tester from us.
Protective Relay Test Sets Switchgear, or relay testers, are ideal for testing Single, 3, 4 and 6 Phase protection relay systems. Commissioning tools compliant for IEC 61850 environments, high burden electromechanical relays, GPS and IRIG-B can be completed by all-in-one test sets. installation of protection relays. Installation of protection relays at site creates a number of possibilities for errors in the implementation of the scheme to occur. Even if the scheme has been thoroughly tested in the factory, wiring to the CTs and VTs on site may be incorrectly carried out, or the CTs/VTs may have been incorrectly installed.

 

The TEST-330B Portable Three Phase Secondary Current Injection Protection Relay Test Set is a multipurpose, light-weight, field portable test set capable of testing a wide variety of electro-mechanical, solid state and microprocessor-based protective relays, motor overload relays, and similar protective devices.

The Test-330B Portable Three Phase Secondary Current Injection Protection Relay Test Set is the first choice for applications requiring very high accuracy more than 0.1%. This unit is not only an excellent test set for protection devices of all kinds but also a universal calibrator. It can as a ac or dc current source and voltage, 0-10A, 0-130V accuracy 0.1%.

 

Its unique accuracy and reliability make the Test-330 ideal for protection and measurement equipment manufacturers for research and development, production and electric power company type testing.

 

The TEST-330B test system has the ability to be manually controlled with GFUVE'S Relay Testing Management Software. The device with its large, full color, high resolution, TFT LCD touch screen allows the user to perform manual, steady-state and dynamic testing quickly and easily using the manual test screen, as well as using built-in preset test routines for most popular relays.

 

FEATURES

  • Embedded host machine equipped with Complex Programmable Logic Device (CPLD)
  • Eight-path synchronous D/A output in a single machine
  • High-accuracy linear power amplifier
  • Host machine integrated single cabinet structure with big LCD screen and complete interface has obtained appearance patent
  • Intelligent self-protection function
  • Plentiful Binary and powerful software function
  • Easily complete the ABB, Siemens, AREVA, Schneider, GE, SEL, VAMP, Toshiba, NR, Sifang and other foreign manufacturers of protective device test
  • Synchronous output of five-phase voltage and three-phase current, Max AC current output is 90A, Max AC voltage output is 260V

 

OVERVIEW

 

  • 3 phase current output
  • 5 phase voltage output
  • 8 binary input, 4 binary output
  • Accuracy more than 0.1%

 

TEST ITEM

  • Differential protection
  • Distance protection
  • Zero sequence protection
  • Setting group test
  • State sequence
  • Synchronization test
  • Special test
  • Oscillation test
  • Metering instrument
  • Hardware checkout
  • Low Voltage protection
  • Fault Waveform Reproduction
  • U/I test
  • DC test
  • Impedance characteristics
  • Power direction test
  • I-T test
  • Differential relay
  • Harmonic test

 

PARAMETERS

 

Electrical parameters
Power voltageAC220V±10% , 50/60Hz±10%
Time measurement0.1ms-999999.999s
AC current output 
Phase current output (effective value)3 x 0-30A
Maximum power output260VA/phase
Maximum parallel current output (effective value)0-90A
Long-term allowable working value of phase current
(effective value)
>10A
Allowable working time of maximum current>11s
Accuracy class<±0.1%
AC voltage output 
Phase voltage output (effective value)5 x 0-130V
Line voltage output (effective value)0-260V
Maximum power output70VA/phase
Accuracy class<±0.1%
DC current output 
Output range-10 to 10A or 3 x 0 to ±10A
Maximum power output200VA
Accuracy class<±0.1%
DC voltage output 
Output range0-300V or 5 x 0 to ±130V
Maximum output power130VA
Accuracy class<±0.1%
Binary input 
Idle contact1-20mA, 24V (DC)
Electric potential contact250V/0.5A (DC)
Binary output 
Idle contact250V/0.5A (DC)
Rated output 
Frequency error<±0.001Hz
Phase error<±0.1%
Waveform distortion<±0.3% (fundamental wave)
Time error<40µs
Output frequency0-1050Hz
Superposed harmonic wave0-21times
Mechanical parameters 
Dimensions (L×W×H) (mm)360x195x375
Weight (kg)16.6
Environmental conditions
Use range0°C to 45°C
Storage range-25°C to 70°C

Photo

Hot Products

LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20 ...
LZCK-55 Outdoors Split Core Current Transformer Description LZCK series current transformers are ...
Outdoor split core current transformer 3000A LZCK series outdoor waterproof current transformers are ...
LZCK-36 OUTDOORS SPLIT CORE CURRENT TRANSFORMER Description The model LZCK-36 outdoor split core ...
Split Core Current Transformer LZCK185-10 LMCK series outdoor current transformers are applicable ...
LZCK-55 IP67 Outdoor split core current transformer 200/5A 0.5S for three Phase Watthour meter LZCK...