Water Pumps Three Phase Voltage Monitoring Relay 380V protector 1CO 6A contact capacity

 

Phase sequence protector is a multi-function three-phase power system or three-phase power equipment monitoring and protection equipment.


The phase sequence protector can display the three-phase power supply voltage in real time, and can output through the relay when the power supply overvoltage protection, undervoltage protection, phase loss protection, unbalance protection, fault phase protection, PTC temperature protection, load side protection and other faults occur. The form provides the user with an alarm output and the contact control signal output by the protection circuit action, which functions as an alarm and protection. Sets three-phase voltage display, over-voltage protection, under-voltage protection, phase loss protection (phase-failure protection), voltage imbalance protection, phase sequence protection (wrong phase protection) in one, using a powerful microprocessor chip and non-easy Loss of storage technology, display using high-definition ultra-wide temperature Chinese liquid crystal, with full-featured, stable performance, intuitive display, easy operation.

 

Phase sequence protection device can be divided into two types: contact phase sequence protector and non-contact phase sequence protector. The former uses electromagnetic relays or AC contactors as its actuators, while the latter uses solid-state relays (thyristors, IGBTs, high-voltage VMOS transistors) as its actuators. The former uses the contacts of an electromagnetic relay or AC contactor to break the phase-sequence faulty three-phase power supply, while the latter uses an electronic component to turn off the faulty power supply. Therefore, compared with the former, the latter has the characteristics of fast response, no noise, no spark, long life, small size, and high mechanical strength. The former is relatively the latter, has a high breakdown pressure, withstand overload, low cost, etc. Features.

 

 

♦ Features

-- Built-in LCD and keypad afford a precise,digital setting

-- Three-phase monitoring of phase sequence, phase loss, over- and undervoltage and phase unbalance

-- Adjustable over- and undervoltage, phase unbalance threshold

-- Independent adjustable delay time for overvoltage, undervoltage, phase unbalance

-- Powered by the measuring circuit

-- 1 NO & 1NC contacts

-- Faulure recording

 

♦ Protective Functions

-- Phase sequence

-- Phase loss

-- Phase unbalance

-- Overvoltage

-- Undervoltage

 

♦ Typical Applications

• Pumps • Fans

• Blowers • Motors

• Compressors

 

♦ Approvals

• CE • CCC

 

♦ Technical data

 

TypeJVR1000
Measuring circuitL1,L2,L3
Rated voltage380VAC ,50Hz
Monitoring functionsphase sequence, phase loss, overvolatege, undervoltage,phase unbalance
Overvoltage setting range390-490V adjustable
Undervoltage setting range300-470V adjustable
Hysteresis10V
Delay time for overvoltage and undervoltage0.1-25s adjustable
Phase unbalance setting range5%-29% adjustable
Delay time for phase unbalance1-25s adjustable
Delay time for phase loss1s
Delay time for phase sequenceinstant
IndicatorsLCD indicating voltage,current,operation status
Output contacts1 NO,1NC
Contact capacity6A ,250VAC
Dimensions (H x W x D)80×40×54mm
MountingDIN rail

Hot Products

Three Phase Current Monitoring Relay WDB-1F Motor Over Under Voltage Protector ♦ Features -- ...
120 Volt Overcurrent Current Balance Relay Integrative Structure For Blowers Protection function ...
Phase Unbalance Current Monitoring Relay Integrative Structure For Compressors ♦ Features -- ...
Fans current limiting relay , 40A Phase Failure Protection Relay Integrative Structure ♦ Features -- ...
Overload Current Monitoring Relay 1 NC SCR Output Contact LED Indication JDB-1 series motor ...
Unbalance Current Control Relay 220V 380V With Knob Setting Method With 4 LEDS 1 Features Integrativ...