Home Companies Wuhan Rising Electric Co., Ltd.

6 Phase Electronic Protective Relay Test Equipment 1 Year Warranty

Wuhan Rising Electric Co., Ltd.
Active Member

Contact Us

[China] country

Address: 1st Floor, Block B, Innovation Park, Changzui Science and Technology Park, Sixth High-tech Road, Jiangxia District, Wuhan City, Hubei Province

Contact name:Jason

Inquir Now

Wuhan Rising Electric Co., Ltd.

6 Phase Electronic Protective Relay Test Equipment 1 Year Warranty

Country/Region china
City & Province wuhan hubei
InquireNow

Product Details

RS1200 Six Phase Secondary Injection Microcomputer Protective Relay Tester With 1 Year Warranty

Product Description

Wuhan Rising Electric.,CO is specialized in manufacturing all grades of transformer testing equipment, load no-load transformer characteristic tester, automatic ratio groups of test instrument, transformer winding deformation tester, power frequency testing transformer, automatic anti jamming tester, series resonance test device, partial discharge detection device, insulating oil dielectric strength tester, etc With abundant of experience and professional team we have exported our products to many countries and regions all over the world, especially the Middle East area, Asian area. Eastern Europe, etc. Also our products are widely recognized and trusted by users.

Rated Parameters/Function

The index is designed to guide the tester that all kinds of the relay protection device test can be done by the following series which modules of software.

Relay test:

Relay protection typeTest ItemProposed test moduleRemarks
Signal relayCorresponding test items

DC Test

 

AC and DC Test

If the intermediate relay is required AC/DC hybrid input, please test in ‘The AC And DC Test ‘module.

If Rated current of the signal relay is too small, please use the voltage loop output of tester to do experiments.

Time relay
Intermediate relay
Coincidence relay
Other DC voltage and current relay
Current relayCorresponding test itemsAC Test

The sequence component relay can be tested in the special sequence module of ‘AC Test’.

The inverse time relay can be tested in the "It characteristics" module.

Over (under) voltage relay
Sequence component relay
Synchronous check (or phase comparison) relay
Inverse time current relay
Differential relayDC magnetic feature

Differential Relay, Differential Harmonic,

AC/DC Test, Harmonic Test

Please refer to ‘Appendix 5’ for correct wiring in the test
Harmonic braking feature

Proportional braking feature

 

Differential Relay, AC Test
Power (directional) relayCorresponding test itemsPower Direction &Impedance, AC TestBefore testing the power (direction) relay, the type of connection and the action boundary of the protection should be determined in advance.
Impedance relay
Synchronous relayCorresponding test itemsSynchronization Test, AC TestUA, UC of tester is fixed as the system side and the side to side voltage output for ‘Synchronization Test’ module.
Frequency relayCorresponding test itemsHigh-Low Frequency TestWhen the ‘automatic frequency conversion’ method is chosen in the single machine, the frequency slip value can be measured.

 

Computer protection test:

 

 Relay protection typeTest ItemProposed test moduleRemarks
Line protectionMulti-section over currentCorresponding test itemsAC TestAs long as the method is proper, the tests of most relays and microcomputer protection can be done by the ‘AC Test’ module, which should be selective learning.
Over (under) voltage
Sequence component voltage and current
Frequency device
Power direction protection
Reclosing and tansform faultCorresponding test itemsFull Group Test, State Series, Comprehensive Test of Line Protection of 6-35 KV MicrocomputerRequirement that if the Synchronization check and no-voltage check test is done, the Ux as the side and side voltage output and the tester is to use Ua instead of Ux for testing.
Distance & Zero Sequence Protection,The Setting value verification of Distance & Zero Sequence ProtectionDistance & Zero Sequence Protection, Full Group Test, AC Test"Distance & Zero Sequence Protection” can automatically test multiple sections, various fault types and other distance and zero sequence value.
Characteristic of ImpedanceCharacteristic of Impedance
Power frequency variation distanceSetting value verificationDistance & Zero Sequence ProtectionThe fault current should be large enough, such as 10~15A (when CT is 5A)
Compound voltage blocking(directional) overcurrentOver current, low voltage, negative sequence voltage, sensitive angleAC Test, Comprehensive Test of Line Protection of 6-35 KV MicrocomputerSome of the protection of the "low voltage" and "negative sequence voltage" input by different terminal, replacing the wiring is necessary in the test.
Low cycle, low voltage load shedding deviceCorresponding test itemsHigh-Low Frequency Test, Comprehensive Test of Line Protection of 6-35 KV MicrocomputerIf other conditions are satisfied, the device cannot move, please confirm whether the device also need to input current and switch contacts
The generator transformer protectionDifferential protectionProportional braking characteristicDifferential Protection, Differential Value, AC Test

When the differential protection is used in the differential protection of generator, it can be regarded as the transformer protection with the connection type of Y/Y, high and low voltage side balance coefficient of 1.

"Differential protection" module pay attention to the curve characteristic search and the "differential value" module focuses on the differential value test. Their combination can test the differential protection.

Harmonic braking characteristicDifferential Protection, Differential Value, Harmonic Test
Loss of magnetic protectionCorresponding test itemsAC TestThe angle of output voltage and current should be paid attention in the test.
Excitation protection
Other protectionAutomatic quasi synchronization deviceCorresponding test itemsSynchronization TestTo do the automatic adjustment test, the line must be in accordance with the requirements of instruction when testing the input.
Busbar differential protectionCorresponding test itemsAC TestPlease see the instructions of the BP-2B and RCS-915 of "Nari part protection" on in the Appendix 6.
Optical fiber line differential protectionBefore the test to determine whether the device to form a "self loop", if, then the protection of the action value should be equal to half of its set value.

Hot Products

RS2571 Digital Ground Resistance Tester Product Description The instrument applies to power industry...
RSBX-H High Precision SFRA Test Equipment / Transformer Winding Deformation Tester Product ...
RSRS-V Transformer capacity and no-load/load tester Product Description RSRS-V can test the ...
RSJS-M Transformer Capacitance Meter /Tan-delta Tester Product Description Dielectric Loss ...
RSZZ-5A High Precision Transformer DC Resistance Tester Product Description DC resistance measuremen...
RSZZ-2A Transformer Winding Tester DC Resistance Tester Product Description DC resistance measuremen...