Air Handling System Airflow Switch Waterproof Brass Level

 

Description

 

The flow switch is to instruct the switch of the system according to the flow. Set the upper limit for the flow switch or
When the flow reaches the limit, the flow switch will send out a signal or an alarm, and the system will run or stop. Generally, systems that require flow will use flow switches. Depending on the system, as well as the flow switch model and other factors, the place of use is also different, which should be determined according to the specific situation.

 

KAFS adjustable Airflow Switches are used to control and monitor the flow of air and non-corrosive gases in ducts, ideal for ducts, air conditioning and air handling systems


Application

 

Control and monitor air and non aggressive gases flow in ducts, chambers, etc.,of heating, cooling, and air conditioning equipment.


Features

 

● Renovated SPDT micro switch ensures the reliable switch function

● Stainless steel paddle

● Cut-in and cut-out

● Brass level

● IP65


Technical data

 

ModelKAFS
Type of operationOn/Off,single-stage,micro switch
Flow rate switching 
- Cut-outMin. 1.0 m/sec, Max. 8.0 m/sec
- Cut-inMin. 2.5 m/sec, Max. 9.2 m/sec
Flow rate setting adjustmentInternal screw
Sensing elementPaddle
Paddle size3.2 x 6.9 in. (80 x 175 mm)
Paddle w/level - Length7.9 in. (200 mm)
Flow applicationsAir and non aggressive gases
Paddle materialStainless steel
Paddle level materialBrass
Permissible ambient temperature 
- Housing-40℉ to 185℉(-40℃ to 85℃)
- Paddle14℉ to 185℉(-10℃ to 85℃)
Permissible ambient humidity10...90%RH,non-condensing
Cable entryM18 fitting
Housing - MaterialBase:Steel,galvanized; Cover:ABS,fire retardant or PC
- Colorwhite
- ProtectionIP65
InstallationDuct mounted
Ship weight0.7kg

Installation

 

The flow switch should be mounted into a duct or chamber where the air paddle can freely point horizontally downwards. To avoid air swirl and paddle instability, straight zones should be provided for a length of 5 times the diameter of duct upstream and downstream from the installation location.

 

Note:

 

The units are factory calibrated to the minimum switch-off value. To increase the set value, adjust the range screw clockwise. Due to the risk of fracture at air speeds of higher than 5.0 m/sec, the paddle must be cut off on the marked side. When the paddle is cut off, the minimum cut-out value increases from 1.0 m/sec to 2.5 m/sec.


Electrical Wiring

 

 


Dimensions (mm)

 

 

FAQ

 

1 Q: What's the delivery time?

A: According to the specification and quantity of your order, generally 4

days for normal standard products within 10pcs.

 

2 Q:Are you manufacturer or trading company?

A: We are manufacturer with many years of experience.We have our

own factory.Welcome to visit our factory.

 

3 Q: Can we use our logo on the products?

A: Yes.We can provide OEM service.

 

4 Q: Do you have products with ex-proof certificate?

A: Yes,we can offer intrinsic-safety and flame proof certificates.

 

5 Q: What is the warranty of your products?

A: Normal is 12 months.

 

6 Q: What's the means of transport?

A: Express such as TNT,Fedex,DHL,UPS, or logistics by indicator.

 

Hot Products

Resplaceable greystone differential pressure transmitter Description Differential Pressure (DP) ...
The KDP210 differential pressure transmitter has high precision, ultra-low & adjustable range, fast ...
Micro differential pressure sensor Description KDP210 differential pressure transmitter has a ...