4000W Cabinet Type Air Conditioner Door / Side Embeded

 

Product Introduction                                                          

Cabinet air conditioner service object is mainly electrical, mechanical equipment.
Electrical equipment at work due to the role of current will usually heat, and the temperature is too high will affect the service life and reliability of electrical components, and will make the insulation device premature aging, or reduce the insulation value, so that a part of the conductor resistance becomes large, heat and burn. Usually electrical components will be marked with the maximum service temperature, or different temperature corresponding to different performance.
The service object of the cabinet air conditioner is electrical, electronic or mechanical components, rather than people, so the setting temperature can be set very high, between 30℃~45℃, the general default temperature is 35 ℃, and the electrical components of wind speed, noise has no requirements, in fact, the larger air circulation in the cabinet can reduce the local heat island phenomenon of electrical components, contribute to the heat dissipation of electrical components. In addition to outdoor cabinets, most cabinets are installed indoors, and some production environments are complex, such as high temperature, high humidity, high dust, and even oil pollution or corrosive gas. In particular, the phenomenon of high temperature and high dust is relatively common. The working environment temperature of cabinet air conditioners is usually higher than 42℃, and the maximum temperature is 70~80℃, and the following grade requirements should be met: For example, it can work continuously for 24 hours, stronger than civil products, more extensive voltage requirements and so on, which also requires that the cabinet air conditioner must be able to meet the reliability requirements for use in this complex environment.

 

Features                                                                                   

Energy efficient
Large air volume, high efficiency heat ratio;
R410A environmentally friendly refrigerant;
DC inverter high-efficiency compressor, high-efficiency centrifugal fan, electronic expansion valve throttling;
Large-area coil heat exchanger, with smooth air flow, uniform heat exchange and high heat exchange efficiency;
Unique air supply design to optimize the temperature field and flow field distribution of the air in the cabinet;

 

 

 

Application                                                                          

Computer room and small data center;
Computer room cabinets of government enterprises and institutions;
Residential, community cabinets;
Communication base station, machine room cabinet.

 

Technical Specification                                                        

Model EA-300
Power Supply( V,Hz) 1P 220,50
Dimension (mm)W286
H445
D175
Cooling Capacity 300W
Running Current 1.48A
Starting Current 6.5A
Power 287W
Refrigerant Type R134a
Noise Level 55dB
Cabinet Protection Rationinternal circuitIP34
external circuitIP33
Cabinet Temperature Limits 25℃~38℃(Factory Set 30℃)
Ambient Temperature Limits -5℃~43℃
Power Connection Triangle Power Plug( 2 Meters Length)
Weight 15Kg
Color RAL 7035(Light Gray)
Flow Rateinternal circuit70m3/h
external circuit150m3/h
Temperature Control Type Digital Display

Test condition: dry bulb temperature inside the cabinet 35 ℃, wet bulb temperature 26 ℃;

dry-bulb temperature outside the cabinets 35 ℃

 

Factory View                                                                          

 

Packing&Delivery                                                                          

 

Case                                                                         

 

 

 

 

 

 

 

 

Hot Products

Precision Air Conditioning Cooling System For Large Computer Rooms IDC Internet Data Center Product ...
Precision Laboratory Precision Air Conditioner And Constant Temperature And Humidity Air Conditioner ...
Precision Air Conditioner Designer Solution In Computer Room Product Introduction The computer room ...
Precision AC Air Conditioning For Telecom And Data Center Products Introduction Coolnet precision ...
Server Air Conditioner Cooling Machine For Telecommunications Network Product Introduction Sever air ...
Computer Room Air Handler For Telecom And Data Center Product Introduction Computer Room Air Handler ...