1. Specification of genset |
Genset Model | GP17PS |
Prime Power(KW) | 15KVA/12KW |
Rated Voltage(V) | 380V |
Rated Current(A) | 30.4 |
Rated Frequency(HZ) | 50 |
Power Factor(COS) | 0.8(lagging) |
Rated Speed | 1500rpm |
Dimensions(mm) (L×W×H) -- silent type | 2050×950×1420 |
Genset Weight(kgs) -- silent type | 900 |
Noise Level @ 7 m | 70db (A) |
2. Specification of diesel engine |
Engine Brand | Perkins |
Engine Model | 403A-15G2 |
Number of Cylinders | 3 |
Cylinder Arrangement | “L” Type |
Cycle | Four stroke |
Air intake System | Naturally aspirated, Air/Water cooling |
Fuel System | Indirect injection |
Maximum Prime Power at Rated RPM | 20.3KW (27.6BHP) |
Bore×Stroke (mm×mm) | 84x 100 |
Displacement (Liter) | 2.216 |
Compression Ratio | 23.3:1 |
Speed Governor | Electronic |
Cooling System | Water Cooled |
Lub. oil capacity (L) | 10.6 |
Fuel Consumption at 100% Load (L/h) | 5.3 |
Starting Method | DC24V electrical starting |
3. Specification of alternator |
Alternator Brand | Stamford |
Alternator Model | PI144D |
Number of Phase | 3 |
Connecting Type | 3 Phases and 4 Wires |
Number of Bearing | 1 |
Maximum Capacity | 22KVA |
Rated Speed | 1500RPM |
Protection Grade | IP23 |
Altitude | ≤1000m |
Exciter Type | Brushless ,Self-exciting, AVR automatic voltage regulating,100%
Copper winding wire |
Insulation Class | H |
TIF | ≤50 |
THF | ≤2% |
Voltage Regulation, Steady State | ≤±1% |
Transient State Voltage | ≤-15%~+20% |
4. Specification of control Panel |
HGM6110K series Genset controller integrating digital, intelligent
and network techniques is used for automatic control system of
diesel generator. It can carry out functions including automatic
start/stop, data measure and alarm protective. The controller uses
LCD display, optional Chinese, English, Spanish and Russian display
interface with Operation easy and reliable. HGM6110K series Genset
controller uses micro-processing technique which can carryout
precision measure, constant value adjustment, timing and threshold
setting and etc. functions. It can be widely used in all types of
generator automatic control system for compact structure, advanced
circuits, simple connections and high reliability,can be widely
applied to various types of generating units automation system. |