UL Approved 120/ 277/ 347Vac input Automatic Dimming Motion Sensor
For more details, pls refer to as follows:
MC613V D 99 Spec 2023.03.18.pdf
【Product Feature】
- With mini sensor detector, which does not block light
- Low transmitting power, no harm to human
- Support Remote Controller and DIP switch to adjust parameters
- low side lobe; better adaptability to metal warehouse; Strong
anti-interference ability
- 0-10V match MS01 can achieve daylight harvesting function
- Not affected by temperature, humidity, noise, dust etc.
【Function】
√ON-OFF function | ○Daylight harvesting |
√2-step dimming | ○Daylight priority |
√3-step dimming | ○High-low sensitivity |
○override function | ○Grouping |
【Product Information】
body | Tpye A sensor | Tpye B sensor |
Tolerance: ±0.3mm |
【Installation Instruction】
Tpye
A sensor
Tpye B
sensor
Note |
The sensor is allowed to be connected to one load only. The sensor
may be damaged if connecting more than one load. Sensor antenna should be above LED tray. |
【DIP Setting】
【Detection Range】
【Parameter】
Input |
Rated Voltage | 120/277/347VAC 50/60Hz |
Stand-by Power | ≤1W |
Surge Test | 1KV(L/N, EN61000-4-5) |
Output |
Output dimming Mode | 0-10VDC Dimming Signal | ON/OFF Signal |
Load Capacity | @120VAC 3.6A Ballast @277VAC 3.4A Ballast @347VAC 3.3A Ballast |
Max. Surge Capacity | 50A (50% Ipeak, twidth =500us, 230Vac full load, cold start) |
Dim interface |
0-10V Dimming | < 50mA(Non-constant source) 10%(0.5-1V) 20%(1.9-2.1V) 30%(2.9-3.1V) 40% (3.9-4.1V) |
Sensor Parameter |
Operating Frequency | 5.8 GHz ±75MHz, ISM wave band. |
Transmitting power | 1mW Max. |
Detecting Radius | 1m/s ≥2.5m. @ 3m ceiling mounting, 1m/s ≥4m @ 2m wall mounting Test conditions : the product is set to 100% sensitivity, and there
is no obvious occlusion in the room of 60㎡, 165cm person. |
Mounting Height | 3-6m (ceiling mounting) |
3db beam angle | 80°@XZ plane |
96°@YZ plane |
Environment |
Operating Temperature | -35~70℃ |
Storage Temperature | -40℃~80℃, Humidity: ≤85%(Non-condensing) |
Certificate Standard |
Certificate | UL, CE, RED |
Environmental Requirement | Compliant to RoHS 2.0, Reach |
Safety Standards | UL60730 |
IP Rating | IP20 |
Protection Class | Class II |
Other |
Wiring | Press-in terminals wire diameter: L /N /L’: 18AWG +/-Dimming port:
22AWG |
Installation | Built-in |
Package | Clapboard + Carton(K=A) |
Net Weight | 120±5g |
Lifetime | 5 years warranty @Ta 230V |
【Remote】
【Initialization】
- Switch function/three-stage dimming function: the light will be
turned on 100% brightness by the initial energizing sensor, and
will be turned off after 10 seconds. During initialization, no
external motion sensing signal will be detected.
- Two-phase dimming function: the light will turn on 100% brightness
in the initial energizing sensor, and turn to low brightness 10
seconds later (the brightness set by stand-by dim level). During
initialization, no external motion sensing signal will be detected.
【Default setting】
Sensitivity: 100%, Hold time: 8s, Daylight sensor: Disable, Stand
by period: 0s, Stand by DIM level: 10%
【Application Notice】
- Sensor should be installed by a professional electrician. Please
turn off power before installing, wiring, or setting the DIP
switches.
- Microwaves cannot penetrate metal. Do not place product in a closed
or a half-closed metal lamp. Neither metal nor glass is not allowed
to cover above the product. If antenna needs to pass through the
metal plate, please ensure that the top of sensor is close to the
metal plate.
- Sensitivity area is related to moving speed of objects, size of
moving objects, mounting height, mounting angle, working
environment, reflecting materials and etc.. Given detecting area is
typical value that was measured by 165cm high testers in an indoor
open environment.
- The daylight thresholds are measured on a sunny day without shadow
and in an ambient light diffuse reflection status. Different
environment and climate cause different brightness values that
daylight sensor measures.
- The installation spacing between sensors is recommended to be
greater than 3m, and the installation spacing between sensors and
routers is recommended to be greater than 2m.
- Sensor should not be covered or hided by metal, PCB, LED tray
etc..The spacing between the sensor antenna and surrounding
materials should be greater than 5mm. There should be no metal or
PCB tracks near the sensor antenna, above or below it. The
recommended thickness of cover is 2mm, and keep the spacing between
the sensor antenna and cover is greater than 3.2mm.
- Vibration signals will be regarded as moving signals to trigger
sensor. Installing sensor should be away from the object that
vibrates for a long time, such as large metal equipment, pipes, air
conditioning outlets, exhaust vents, smoke exhaust machine ports,
shaking fans, etc. Pets in detecting area may cause false trigger.
- The antenna surface of microwave module should be away from input
AC, output DC, rectifier bridge, transformer, switch tube and other
high-power devices to avoid high frequency signals affecting the
normal operation of microwave sensor’s antenna.
- Sensor is for indoor use only. The waterproof effect for outdoor or
half-outdoor use will be affected. Wind, rain, and moving objects
may cause false triggering.