All-in-One design, Integrated IEC61850 SV & GOOSE, 6I+7V analog channels output, Inbuilt GPS and IRIG-B, and other advance functions.

  •  With the function of test MU accuracy,time characteristcs,state mark,packet loss rate,harmonic analysis,signal analysis, voltage and current phase detection, transient characteristic verification. Can test all aspects of MU functions and performance.
  •  Except MU test and traditional protection relay by analog input, KF920 also can test IED in intelligent substation which comply with IEC61850 standard.
  • 7 phase voltage and 6 phase current output, Maximum voltage is 310V/phase. Maximum current is 32A/phase(Max 192A in parallel six phase), 13 channel low-level signal output.
  •  Analog signal sampling use industrial-grade high-precision ADC, output accuracy can reach 0.05%. Absolute delay, time jitter test accuracy is better than 1μS.
  •  Perfect self-test and prompt. The system is stable ,device performance will not be changed by long time running; The system can detect abnormal situation and give warning.
  • 12.1 inch touch sreeen, Built-in windows operating system. Compact structure, safe and easy to portable
  •  Can be used as a record and waveform analyzer.
  • Built-in high-precision analog amplifier, Which can provide 6 × 32A AC current source and 7 × 310V AC voltage source.
  • Built-in 100M fiber Ethernet port(2 Pairs,LC Type) and IRIG-B Port(In/Out).
  • Provide merger unit accuracy test function (Amplitude error, Phase error, etc.).
  • Simulate Binary I/O signal (Hard contact or GOOSE), Which comply with merger unit voltage switching,voltage parallel logic function test.
  • Can test Merger Unit time characteristcs ,such as time sending accuracy,time receiving accuracy.
  • Have Message analysis and statistics function which can real-time analyze merger unit output SMV, GOOSE message. Have Protocol consistence test and abnormal message check and statistics function.
  • Can test Merger Unit self-check and error handling mechanism through sampling quality,signal mark in GOOSE , warning information define in Goose signal.
  • Real-time display waveform,binary state and previous switch trip time in message electrical parameter. Mark time scale in SV message through hardware to count and evaluate time dispersion of merger unit SV message.
  • Record message data in 1 minute, analyze/compare time scale and amplitude data of each sampling point, display amplitude and time scale statistical results of error distribution curve and Max error.

 

 

Current output6×32A/phase
Current accuracy

≤±0.05%(0.2A~32A);

≤±0.1mA(0.05A~0.2A)

Current resolutionmA1
Current maximum power

≥160VA/phase

(6×32A/phase)

Current Rise And Fall Timeµs<100
Current frequency rangeHz1 ~1000
Current amplitude and frequency characteristics

Amplitude≤±0.2% (10Hz~45Hz),(65Hz~450Hz);

Amplitude≤±0.05% (45Hz~65Hz);

Amplitude≤±0.5% (450Hz~1000Hz)

Current output time

<5A/phase,continuous output ;

5 ~32A/phase,>180s

Voltage output7×310V/phase
Voltage accuracy

≤±0.05%(4V~310V);

≤±0.2mV

(0.5V~4V)

Voltage resolution

1 mV(0.2V~10V),

10 mV(10V~310V)

Voltage maximum power

≥60VA/phase,

7×310V/phase

Voltage rise and fall timeµs<100
Voltage frequencyHz1~1000
Voltage amplitude and frequency characteristics

≤±0.2% (10Hz~45Hz),(65Hz~450Hz);

≤±0.05% (45Hz~65Hz);

≤±0.5% (450Hz~1000Hz)

Voltage amplifier output timeNorminal voltage condition, output continuous
Synchronization time of Current and voltage output≤10µs
Frequency rangeHz1~1000
Frequency accuracy

<0.5mHz (1Hz~65Hz)

<5mHz(65Hz~450Hz)

<10mHz(450 Hz~1000Hz)

Frequency resolutionHz0.0001
HarmonicHarmonic and DC can be superimposed 2 to 25 times amplitude (less than the rated value)
Phase range0~359. 9°
Phase accuracy±0.05°
Phase resolution0.01°
Low level analog output channel13 channels
Low level analog output rangeAC:0~8Vrms(Effective value)
Low level analog maximum current≥1mA
Low level analog output accuracy

<0.1mV(0.1~0.2Vrms)

<0.05%(0.2~8 Vrms)

Low level analog output amplitude and frequency characteristics≤±0.1%~0.5% (1Hz~1kHz)
Low level analog output resolution≤250µV
Digital output voltage

IEC61850-9-1,IEC 60044:Rated voltage parameter11585(0X2D41);

IEC61850-9-2: Digital 1 is 10mV

Digital output current

IEC61850-9-1,IEC 60044: Rated protection current463(0X 1CF),Rated measurementcurrent 11585(0X2D41);

IEC61850-9-2: Digital 1 is 1mA

Synchronization signal

B-code sending ports ≥ 2pcs;

B-code receiving ports ≥ 1pc;

PPS receiving ports ≥ 1pc;

GPS Port : 1pc;

Synchronization accuracy>0.5us

Test system accuracy0.03%;resolution:0.0001%,0.01´
Test verification Class0.2S
Electronic transformer and MU delay testaccuracy<2us
MU delay jitter testaccuracy<2us
MU transient delay accuracyaccuracy<10us
GOOSE receiving timeaccuracy<0.1ms
Binary I/O receiving timeaccuracy<0.1ms
Power supply100V~260V (AC),DC 125-350V Frequency Range:43~57Hz
Operating temperature -10~+50℃
Humidity 5~95%,non-condensing
Storage and transport temperature -20~+70℃
Altitude ≤4000m
Dimension 358mm×149mm×297mm
Weight <18kg

Hot Products

System Description K68i Relay Tester is new mode of All-in-One testing systems on relay protection ...
Able of what K31 series can test Items ANSI® No. IEC61850 numerical IEDs relay & merge unit Distance ...
Able of what K68 series can test Items ANSI® No. Distance protection relay 21 Synchronising or ...
rief instructions for templates installation and usage method: 1. Decompressing the "template_V3.x.x...
Part One: Features 1.All types of voltage, current, frequency, power, impedance, harmonic, ...
a. Current 1. No. of Generators 6 no. 2. Capacity 6x30A /3x60A /1x180Awithout using external ...