Quick Detail of Solenoid Driver

 

 

Manufacturer : Pepperl+Fuchs
Solenoid Driver KFD2-SL2-Ex2.B
2-channel isolated barrier
24 V DC supply (Power Rail)
Output 45 mA at 11.7 V DC
Logic input, non-polarized
International approvals
IECEx approval : IECEx TUN 04.0001
Approved for : [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Shipping Weight : 2 Kg

 

Description of Solenoid Driver

 

This isolated barrier is used for intrinsic safety applications. The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area.
It is controlled via logic signals. The inputs have two defined states: 1-Signal = 16 V DC ... 30 V DC, 0-Signal = 0 V DC ... 5 V DC. The current consumption of the input is about 3 mA. At full load, 11.7 V at 45 mA is available for the hazardous area application.

 

 

Specification of Solenoid Driver

 

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Power consumptionmax. 3.3 W at 45 mA output current
Input
Connection sidecontrol side
Connectionterminals 7, 8, 9
Input currentapprox. 3 mA at 24 V DC
Signal level1-signal: 16 ... 30 V DC
0-signal: 0 ... 5 V DC
Output
Connection sidefield side
Internal resistor272 Ω
Current≤ 45 mA
Voltage≥ 11.7 V
Open loop voltagemin. 24 V
Connectionterminals 1+, 2-, 3- channel 1 ,
terminals 4+, 5-, 6- channel 2
Output rated operating current45 mA
Output signalThese values are valid for the rated operating voltages from 20 ... 30 V DC.
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Power supply/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility 
 Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 50 °C (-4 ... 122 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateZELM 00 ATEX 0024
 MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
 OutputEx ia
 Voltage28 V
 Current110 mA
 Power770 mW (linear characteristic)
Supply 
 Maximum safe voltage40 V (Attention! The rated voltage can be lower.)
Input 
 Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Collective error message 
 Maximum safe voltage40 V (Attention! The rated voltage can be lower.)
CertificateTÜV 02 ATEX 1820 X
 MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation 
 Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
 Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity 
 Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000
International approvals
CSA approval 
 Control drawing116-0304
IECEx approval 
 IECEx certificateIECEx TUN 04.0001
 IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

 

Feature of Solenoid Driver

 

·2-channel isolated barrier
·24 V DC supply (Power Rail)
·Output 45 mA at 11.7 V DC
·Logic input, non-polarized
·Up to SIL 2 acc. to IEC/EN 61508

 

 

Advantage of Our Team

 

Best possible prices and delivery time

Long time experience in the field

Well trained staff

Own warehouse facilities

Best relationships with branch office of manufacture

Flexible and individual service for you

Cheap and safe forwarder for shipments (air)

 

Frequently Asked Questions:

 

Q: Does your goods are new and original?

A: Yes, they are new and original.

 

Q: How long warranty?

A: One-year warranty.

 

Q: Does any certificates can be provided?

A: Yes, it depends on what product you request, please check details with us.

 

 

Hot Products

Proline Promag PTFE Liner Electromagnetic Flowmeter 5P2B1F-AAACCAEA1K0A​ 5P2B1F-AAACCAEA1K0A Proline ...
Proline Promass Coriolis Flowmeter 8F2B80-BBEEBASAABSA+AADCJBJC 8F2B80-BBEEBASAABSA+AADCJBJC Proline ...
230VAC E&H Instrument CM442 CM442-AAM1A2F010A+AA Transmitter CM442-AAM1A2F010A+AA 1-/2-Channel ...
CLS21D E&H Instrument Digital Conductivity Meter Condumax CLS21D-C1E1 Digital Conductivity Sensor ...
25bar 2.5MPa E&H Instrument Absolute And Gauge Pressure Cerabar PMP23 PMP23-AA1U1RBWSJ+QJ Absolute ...
HART 4 Channel Transmitter Liquiline CM444 Enclosed Cable Entry CAM21A3FG11BAA 4-Channel Transmitter ...