ABB I/P Signal Converter for Standard Signals TEIP11-PS V18311H-182210100

 

 

 

Description:

■ Reliable through well-proven concept
– More than 1,000,000 times in use
■ Compact design
– Small dimensions, low weight
■ Robust in terms of construction and function
– Influence of shock and vibration < 1 % at 10 g
■ Various signal ranges
– Input e.g. 0...20 mA or 4...20 mA
Output 0.2...1 bar or 3...15 psi
■ Complies with the following directives
– EMC directive 89/336/EEC as of May 1989
EC directive for the CE conformity certificate
■ Wide operating temperature range
– From -40 °C (optionally -55 °C) to +85 °C
■ Explosion protection certificates,
for worldwide use
– ATEX, FM/CSA, GOST
Intrinsically safe or flameproof
■ Various models
– Control room housing, IP 20, for rail mounting
– Control room housing, IP 20, for block mounting,
– Plastic field housing, IP 54
– Aluminium or stainless steel housing, IP 65
■ Single unit
– For OEM applications (on request)

 

 

Technical Data
Input
Signal range
0...20 mA or 4...20 mA
0...10 mA or 10...20 mA or 4...12 mA or 12...20 mA
(other ranges on request)
Input resistance
Ri = 260 ohms at 20 °C, Tk + 0.4 %/K
Overload limit
30 mA (refer to specifications under “Explosion protection”
for devices with explosion protection approval)
Capacitance/Inductance
negligible
Output

 

 

Signal range
0.2...1 bar or 3...15 psi
0.4...2 bar or 6...30 psi
(other ranges on request)
Air capacity (max.)
≥ 5 kg/h = 4.1 Nm3 /h = 2.4 scfm
Load characteristic to VDE/VDI 3520
≥ 0.95 kg/h = 0.9 Nm3 /h = 0.5 scfm
Air supply
Instrument air
free of oil, water and dust to DIN/ISO 8573-1
pollution and oil contents according to Class 3
dew point 10 K below operating temperature

 

 

 

Supply pressure
1.4 ± 0.1 bar or 20 ± 1.5 psi (for output signal 1 bar or 15 psi)
2.5 ± 0.1 bar or 40 ± 1.6 psi (for output signal 2 bar or 30 psi)
Air consumption
≤ 0.2 kg/h = 0.16 Nm3 /h = 0.1 scfm
Transmission data and influences
Characteristic
linear, direct or reverse action
Deviation
≤ 0.5 %
Hysteresis
≤ 0.3 %
Dead zone
≤ 0.1 %
Temperature
≤ 0.5 % / 10 K between -20 and +85 °C
≤ 2 % / 10 K between -55 and -20 °C
Air supply
≤ 0.3 % / 0.1 bar pressure variation
Mechanical vibration
≤ 1 % up to 10 g and 20...80 Hz
Seismic vibration
meets requirements to DIN IEC 68-3-3 class III for strong and
strongest earthquakes

 

Hot Products

Benefits Robust electrode with long poison diffusion path, requires low maintenance due to large, ...
Benefits Liquiline CM42 features the following protocols and interfaces: 0/4...20 mA HART PROFIBUS ...
Measuring principle Conductive Application Water, waste water, process Characteristic 4-wire ...
Detailed Product Description Process Temperature: -40 °C ... 150 °C (-40 °F ... 302 °F) Process ...
Detailed Product Description Max. Measurement Error: ±0,5% O.r. ± 2 Mm/s (±0,5% O.r. ± 0,08 In/s) ...
Endress Hauser Measuring Cable CYK 71 10m 50088281 Manufacturer : Endress+Hauser Use:digital ...