Rail-Mount Temperature Transmitter TTR200 For ABB
Approvals for explosion protection | ATEX, IECEx, zone 0 |
Output signal | 4 to 20 mA, HART |
Universal sensor input | RTD, thermocouple, Ω, mV |
Overview
The TTR200 is a rail-mount version of the TTH200 transmitter with
the addition of two indicator LEDs. A green LED indicates that the
transmitter is powered. A red LED would indicate a fault in either
the unit or the sensor. TTR200 units can be placed in cabinet
racks. It can be configured with ABB-tools such as DAT200 (Asset
Vision Basic) via DTM, Handheld via EDD, FIM (Field Information
Manager) or any standard tool using FDI-/FDT-Technology.
Data
- Universal sensor input
– RTD, thermocouple, Ω, mV - Functional safety SIL 2 / SIL 3 in accordance with IEC 61508
- Output signal
– 4 to 20 mA, HART - Accuracy 0.1 %, long-term stability 0.05 % per year
- Wire break / corrosion monitoring in accordance with NE 89
- Diagnostic information in accordance with NE 107
- Approvals for explosion protection
– ATEX, IECEx, zone 0
– FM / CSA
– GOST