Wuhan Huaying Electric Power Tech & Science Co., Ltd |
|
High Security Transformer Testing Equipment Transformer Winding Resistance Test 20A
2. Equipment Description:
There are four DC currents to select for HYZC-20A which has a
large output power, the power of the tester itself is very little.
Used four lines, it is quick,stable,high precision for testing the
winding resistance.
In addition, it has a strong ability for anti-jamming ,over current
,over voltage and discharge.
The security is also very high, So it is a ideal tester for testing
various resistances especially the sensibility equipment.
The tester has functions of self test, data processing, discharge
rapidly, result print and so on.
3. Technical Parameters:
Resistance precision: | ±(0.2%RGD+2d) |
Test range: | 1.000Ω-1000Ω(20mA) |
The least scale: | 1uΩ |
Output current precision: | ±5% |
RS232 port: | Support for data uploading to PC |
Store: | 200 groups of data can be stored |
Test result print out: | With thermal printer to print the test data |
Weight: | 10KG |
Power supply: | AC220V±10%,(50±1)HZ |
Operation condition: | -10~50℃ Humidity <90% No condensation |
Operation
1) Open the power switch after connected the test wires,waiting for
several seconds to enter the interface showed by Fig.
3,press[left],[right]to move the cursor,press[OK]to enter the
function.
2) Press[OK]to enter the interface showed by Fig.4,move the cursor
to the current option then press[OK]to select the test current
circularly,the winding resistance test range is showed on the top
of the current options, after selecting the current, press “Start”
to enter the interface showed by Fig.5, it will enter the interface
showed by Fig.4 if [OK]button is pressed.
3) The Fig.6 will be showed if the test is normal, then press [OK]
to stop to test after “Charge OK” is showed on the LCD, thus the
Fig.7 is showed, then click the corresponding cursor to realize the
corresponding function.
4) If the interface showed by Fig.8 is appeared when testing, it
indicate that the resistance is too small, then a bigger current is
needed for correctly testing, if the object is allowed for a bigger
current, increase the current to test it again.
5) If the interface showed by Fig.9-a is appeared when testing, it
indicate that the resistance is bigger than 10 Ω,you cannot use the
tester test the winding resistance that is over 10Ω.
6) If the interface showed by Fig.9-b is appeared when testing, you
should reduce the test current to test the winding resistance
again.
Notice: when finished to test the inductance object, you mustn’t
disconnect the wires directly in case to harm the people or tester.
There is a discharge circle in the tester, when finished test, the
inductance is discharge though it, you can disconnect the wires
until the beep has no voice.
Saved Data
A. View the saved data
When Fig.3 is showed, click “Saved Data” to come into Fig.10, and
then click “View Data” to let Fig.11 interface show, you could view
the saved data by clicking the“”,“”, if you want to print or delete
the current data, move the cursor to it, clicking[OK] is all right.
B. Upload
click“Upload” then open the PC software.
C. Delete all data
click “Delete All”to enter panel. Click“Yes” to delete all
data,Click“No” to return.
Time Setting and View ID Number
Enter the interface showed by Fig.3, click“Time Setting” to enter
Fig.15, in which the ID number is already set, you can not modify
it. If you want to modify one bit of the time, move the cursor to
it, click [OK] and press the direction key to increase or decline
the value, Click [OK]again to release the cursor, if the
current time is not modified, it may save a wrong time when you
save data.