Wuhan Huaying Electric Power Tech & Science Co., Ltd |
|
Portable Intelligent Transformer Test Set On Load Tap Changer Ohmmeter Analyzer
1. Equipment Description:
HYKC-2000 is mainly applied to test transient time, transition waveform, transition resistance, synchronization status of three phase.
2. Main Functions:
1 Test transformers of type Y0 Y Δ and display resistance value directly;
2 Automatically analyze waveform fault and mark the fault.
3 Automatically adjust resistance value and time range according to sampling data
4 Transformer type Δ is able to display to synchronization status of three phase;
5 Be able to test with winding or without winding;
6 Four terminal connection mode and provide high accuracy of resistance measurement.
7 Continuous test to save time of power off
8 Make word report
9 800×480 colorized LCD with touch screen and high speed printer
10 Store 1000 groups of data and also can be saved by USB flash disk
3. Technical Parameters:
Three phase constant current source charge: | charge current: 3A/1A; 0.6A/0.2A |
Maximum voltage of the port: | 24V |
Maximum range of transition resistance: | 100Ω |
Measuring range: | 1A:0.4Ω~20Ω 0.2A:10Ω~100Ω |
Record time of waveform: | 300ms |
Sample rate: | 30k |
Resolution of time: | 0.1ms |
Resolution of resistance: | 0.1Ω |
Accuracy of transition resistance: | ±5% Reading±0.1Ω |
Accuracy of transient time: | ±0.5% Reading±0.2mS |
Temperature: | -10-40°C Humidity: <85%RH |